30 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 5.78V (2.51%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.96V (2.59%)
Voltage at Load224.2 VLine Loss: 173.3 W
Max Power & Breaker6.9 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A38.52 V (16.75%)191.5 V63.54 V (27.63%)1155.6 WDrop High
2.5 mm²24 A18 A23.11 V (10.05%)206.9 V38.12 V (16.58%)693.4 WDrop High
4 mm²32 A25 A14.45 V (6.28%)215.6 V23.83 V (10.36%)433.3 WDrop High
6 mm²41 A32 A9.63 V (4.19%)220.4 V15.88 V (6.91%)288.9 W~ ≤5%
10 mm²57 A44 A5.78 V (2.51%)224.2 V9.53 V (4.14%)173.3 W✓ OK (≤3%)
16 mm²76 A59 A3.61 V (1.57%)226.4 V5.96 V (2.59%)108.3 W✓ OK (≤3%)
25 mm²101 A78 A2.31 V (1.0%)227.7 V3.81 V (1.66%)69.3 W✓ OK (≤3%)
35 mm²125 A97 A1.65 V (0.72%)228.3 V2.72 V (1.18%)49.5 W✓ OK (≤3%)
50 mm²151 A118 A1.16 V (0.5%)228.8 V1.91 V (0.83%)34.7 W✓ OK (≤3%)
70 mm²192 A150 A0.83 V (0.36%)229.2 V1.36 V (0.59%)24.8 W✓ OK (≤3%)
95 mm²232 A181 A0.61 V (0.26%)229.4 V1.0 V (0.44%)18.2 W✓ OK (≤3%)
120 mm²269 A210 A0.48 V (0.21%)229.5 V0.79 V (0.35%)14.4 W✓ OK (≤3%)
150 mm²309 A241 A0.39 V (0.17%)229.6 V0.64 V (0.28%)11.6 W✓ OK (≤3%)
185 mm²353 A275 A0.31 V (0.14%)229.7 V0.52 V (0.22%)9.4 W✓ OK (≤3%)
240 mm²415 A324 A0.24 V (0.1%)229.8 V0.4 V (0.17%)7.2 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.08%)229.8 V0.32 V (0.14%)5.8 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.06%)229.9 V0.24 V (0.1%)4.3 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 30A at 45 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 30A over 45m at 230V (voltage drop: 5.78V or 2.51%).

What is the power capacity of 30A at 230V?

At unity power factor, 30A at 230V supports 6.9 kW with a standard 30A circuit breaker.