30 Amp Cable Size at 35 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 9.73V (2.34%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 10.7V (2.58%)
Voltage at Load405.3 VLine Loss: 505.6 W
Max Power & Breaker21.56 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A25.95 V (6.25%)389.1 V42.8 V (10.31%)1348.2 WDrop High
2.5 mm²24 A18 A15.57 V (3.75%)399.4 V25.68 V (6.19%)808.9 WDrop High
4 mm²32 A25 A9.73 V (2.34%)405.3 V16.05 V (3.87%)505.6 W✓ OK (≤3%)
6 mm²41 A32 A6.49 V (1.56%)408.5 V10.7 V (2.58%)337.1 W✓ OK (≤3%)
10 mm²57 A44 A3.89 V (0.94%)411.1 V6.42 V (1.55%)202.2 W✓ OK (≤3%)
16 mm²76 A59 A2.43 V (0.59%)412.6 V4.01 V (0.97%)126.4 W✓ OK (≤3%)
25 mm²101 A78 A1.56 V (0.38%)413.4 V2.57 V (0.62%)80.9 W✓ OK (≤3%)
35 mm²125 A97 A1.11 V (0.27%)413.9 V1.83 V (0.44%)57.8 W✓ OK (≤3%)
50 mm²151 A118 A0.78 V (0.19%)414.2 V1.28 V (0.31%)40.4 W✓ OK (≤3%)
70 mm²192 A150 A0.56 V (0.13%)414.4 V0.92 V (0.22%)28.9 W✓ OK (≤3%)
95 mm²232 A181 A0.41 V (0.1%)414.6 V0.68 V (0.16%)21.3 W✓ OK (≤3%)
120 mm²269 A210 A0.32 V (0.08%)414.7 V0.53 V (0.13%)16.9 W✓ OK (≤3%)
150 mm²309 A241 A0.26 V (0.06%)414.7 V0.43 V (0.1%)13.5 W✓ OK (≤3%)
185 mm²353 A275 A0.21 V (0.05%)414.8 V0.35 V (0.08%)10.9 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.04%)414.8 V0.27 V (0.06%)8.4 W✓ OK (≤3%)
300 mm²477 A372 A0.13 V (0.03%)414.9 V0.21 V (0.05%)6.7 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.02%)414.9 V0.16 V (0.04%)5.1 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 35 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 30A at 35 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 30A over 35m at 415V (voltage drop: 9.73V or 2.34%).

What is the power capacity of 30A at 415V?

At unity power factor, 30A at 415V supports 21.56 kW with a standard 30A circuit breaker.