⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

30 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 4.17V (1.0%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 4.59V (1.1%)
Voltage at Load410.8 VLine Loss: 216.7 W
Max Power & Breaker21.56 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.12 V (2.68%)403.9 V18.34 V (4.42%)577.8 WDrop High
2.5 mm²24 A18 A6.67 V (1.61%)408.3 V11.01 V (2.65%)346.7 WDrop High
4 mm²32 A25 A4.17 V (1.0%)410.8 V6.88 V (1.66%)216.7 W✓ OK (≤3%)
6 mm²41 A32 A2.78 V (0.67%)412.2 V4.59 V (1.1%)144.4 W✓ OK (≤3%)
10 mm²57 A44 A1.67 V (0.4%)413.3 V2.75 V (0.66%)86.7 W✓ OK (≤3%)
16 mm²76 A59 A1.04 V (0.25%)414.0 V1.72 V (0.41%)54.2 W✓ OK (≤3%)
25 mm²101 A78 A0.67 V (0.16%)414.3 V1.1 V (0.27%)34.7 W✓ OK (≤3%)
35 mm²125 A97 A0.48 V (0.11%)414.5 V0.79 V (0.19%)24.8 W✓ OK (≤3%)
50 mm²151 A118 A0.33 V (0.08%)414.7 V0.55 V (0.13%)17.3 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (0.06%)414.8 V0.39 V (0.09%)12.4 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.04%)414.8 V0.29 V (0.07%)9.1 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.03%)414.9 V0.23 V (0.06%)7.2 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.03%)414.9 V0.18 V (0.04%)5.8 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.02%)414.9 V0.15 V (0.04%)4.7 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.02%)414.9 V0.11 V (0.03%)3.6 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)414.9 V0.09 V (0.02%)2.9 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)415.0 V0.07 V (0.02%)2.2 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 30A at 15 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 30A over 15m at 415V (voltage drop: 4.17V or 1.0%).

What is the power capacity of 30A at 415V?

At unity power factor, 30A at 415V supports 21.56 kW with a standard 30A circuit breaker.