300 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 0.74V (0.18%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.76V (0.18%)
Voltage at Load414.3 VLine Loss: 385.2 W
Max Power & Breaker215.64 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A74.13 V (17.86%)340.9 V122.28 V (29.47%)38520.0 WDrop High
2.5 mm²24 A18 A44.48 V (10.72%)370.5 V73.37 V (17.68%)23112.0 WDrop High
4 mm²32 A25 A27.8 V (6.7%)387.2 V45.86 V (11.05%)14445.0 WDrop High
6 mm²41 A32 A18.53 V (4.47%)396.5 V30.57 V (7.37%)9630.0 WDrop High
10 mm²57 A44 A11.12 V (2.68%)403.9 V18.34 V (4.42%)5778.0 WDrop High
16 mm²76 A59 A6.95 V (1.67%)408.1 V11.46 V (2.76%)3611.2 WDrop High
25 mm²101 A78 A4.45 V (1.07%)410.6 V7.34 V (1.77%)2311.2 WDrop High
35 mm²125 A97 A3.18 V (0.77%)411.8 V5.24 V (1.26%)1650.9 WDrop High
50 mm²151 A118 A2.22 V (0.54%)412.8 V3.67 V (0.88%)1155.6 WDrop High
70 mm²192 A150 A1.59 V (0.38%)413.4 V2.62 V (0.63%)825.4 WDrop High
95 mm²232 A181 A1.17 V (0.28%)413.8 V1.93 V (0.47%)608.2 WDrop High
120 mm²269 A210 A0.93 V (0.22%)414.1 V1.53 V (0.37%)481.5 WDrop High
150 mm²309 A241 A0.74 V (0.18%)414.3 V1.22 V (0.29%)385.2 W✓ OK (≤3%)
185 mm²353 A275 A0.6 V (0.14%)414.4 V0.99 V (0.24%)312.3 W✓ OK (≤3%)
240 mm²415 A324 A0.46 V (0.11%)414.5 V0.76 V (0.18%)240.8 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (0.09%)414.6 V0.61 V (0.15%)192.6 W✓ OK (≤3%)
400 mm²570 A445 A0.28 V (0.07%)414.7 V0.46 V (0.11%)144.4 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 300A at 10 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 10m at 415V (voltage drop: 0.74V or 0.18%).

What is the power capacity of 300A at 415V?

At unity power factor, 300A at 415V supports 215.64 kW with a standard 300A circuit breaker.