300 Amp Cable Size at 60 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 4.45V (1.07%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 4.59V (1.1%)
Voltage at Load410.6 VLine Loss: 2311.2 W
Max Power & Breaker215.64 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A444.79 V (107.18%)0.0 V733.7 V (176.79%)231120.0 WDrop High
2.5 mm²24 A18 A266.87 V (64.31%)148.1 V440.22 V (106.08%)138672.0 WDrop High
4 mm²32 A25 A166.8 V (40.19%)248.2 V275.14 V (66.3%)86670.0 WDrop High
6 mm²41 A32 A111.2 V (26.79%)303.8 V183.42 V (44.2%)57780.0 WDrop High
10 mm²57 A44 A66.72 V (16.08%)348.3 V110.05 V (26.52%)34668.0 WDrop High
16 mm²76 A59 A41.7 V (10.05%)373.3 V68.78 V (16.57%)21667.5 WDrop High
25 mm²101 A78 A26.69 V (6.43%)388.3 V44.02 V (10.61%)13867.2 WDrop High
35 mm²125 A97 A19.06 V (4.59%)395.9 V31.44 V (7.58%)9905.1 WDrop High
50 mm²151 A118 A13.34 V (3.22%)401.7 V22.01 V (5.3%)6933.6 WDrop High
70 mm²192 A150 A9.53 V (2.3%)405.5 V15.72 V (3.79%)4952.6 WDrop High
95 mm²232 A181 A7.02 V (1.69%)408.0 V11.58 V (2.79%)3649.3 WDrop High
120 mm²269 A210 A5.56 V (1.34%)409.4 V9.17 V (2.21%)2889.0 WDrop High
150 mm²309 A241 A4.45 V (1.07%)410.6 V7.34 V (1.77%)2311.2 W✓ OK (≤3%)
185 mm²353 A275 A3.61 V (0.87%)411.4 V5.95 V (1.43%)1873.9 W✓ OK (≤3%)
240 mm²415 A324 A2.78 V (0.67%)412.2 V4.59 V (1.1%)1444.5 W✓ OK (≤3%)
300 mm²477 A372 A2.22 V (0.54%)412.8 V3.67 V (0.88%)1155.6 W✓ OK (≤3%)
400 mm²570 A445 A1.67 V (0.4%)413.3 V2.75 V (0.66%)866.7 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 60 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 300A at 60 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 60m at 415V (voltage drop: 4.45V or 1.07%).

What is the power capacity of 300A at 415V?

At unity power factor, 300A at 415V supports 215.64 kW with a standard 300A circuit breaker.