300 Amp Cable Size at 30 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 2.22V (0.54%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 2.29V (0.55%)
Voltage at Load412.8 VLine Loss: 1155.6 W
Max Power & Breaker215.64 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A222.4 V (53.59%)192.6 V366.85 V (88.4%)115560.0 WDrop High
2.5 mm²24 A18 A133.44 V (32.15%)281.6 V220.11 V (53.04%)69336.0 WDrop High
4 mm²32 A25 A83.4 V (20.1%)331.6 V137.57 V (33.15%)43335.0 WDrop High
6 mm²41 A32 A55.6 V (13.4%)359.4 V91.71 V (22.1%)28890.0 WDrop High
10 mm²57 A44 A33.36 V (8.04%)381.6 V55.03 V (13.26%)17334.0 WDrop High
16 mm²76 A59 A20.85 V (5.02%)394.2 V34.39 V (8.29%)10833.8 WDrop High
25 mm²101 A78 A13.34 V (3.22%)401.7 V22.01 V (5.3%)6933.6 WDrop High
35 mm²125 A97 A9.53 V (2.3%)405.5 V15.72 V (3.79%)4952.6 WDrop High
50 mm²151 A118 A6.67 V (1.61%)408.3 V11.01 V (2.65%)3466.8 WDrop High
70 mm²192 A150 A4.77 V (1.15%)410.2 V7.86 V (1.89%)2476.3 WDrop High
95 mm²232 A181 A3.51 V (0.85%)411.5 V5.79 V (1.4%)1824.6 WDrop High
120 mm²269 A210 A2.78 V (0.67%)412.2 V4.59 V (1.1%)1444.5 WDrop High
150 mm²309 A241 A2.22 V (0.54%)412.8 V3.67 V (0.88%)1155.6 W✓ OK (≤3%)
185 mm²353 A275 A1.8 V (0.43%)413.2 V2.97 V (0.72%)937.0 W✓ OK (≤3%)
240 mm²415 A324 A1.39 V (0.33%)413.6 V2.29 V (0.55%)722.2 W✓ OK (≤3%)
300 mm²477 A372 A1.11 V (0.27%)413.9 V1.83 V (0.44%)577.8 W✓ OK (≤3%)
400 mm²570 A445 A0.83 V (0.2%)414.2 V1.38 V (0.33%)433.4 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 30 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 300A at 30 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 30m at 415V (voltage drop: 2.22V or 0.54%).

What is the power capacity of 300A at 415V?

At unity power factor, 300A at 415V supports 215.64 kW with a standard 300A circuit breaker.