300 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 1.41V (2.92%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.27V (19.3%)
Voltage at Load46.6 VLine Loss: 421.3 W
Max Power & Breaker14.4 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1498.0 V (3120.83%)0.0 V2471.0 V (5147.92%)449400.0 WDrop High
2.5 mm²24 A18 A898.8 V (1872.5%)0.0 V1482.6 V (3088.75%)269640.0 WDrop High
4 mm²32 A25 A561.75 V (1170.31%)0.0 V926.62 V (1930.47%)168525.0 WDrop High
6 mm²41 A32 A374.5 V (780.21%)0.0 V617.75 V (1286.98%)112350.0 WDrop High
10 mm²57 A44 A224.7 V (468.12%)0.0 V370.65 V (772.19%)67410.0 WDrop High
16 mm²76 A59 A140.44 V (292.58%)0.0 V231.66 V (482.62%)42131.2 WDrop High
25 mm²101 A78 A89.88 V (187.25%)0.0 V148.26 V (308.87%)26964.0 WDrop High
35 mm²125 A97 A64.2 V (133.75%)0.0 V105.9 V (220.62%)19260.0 WDrop High
50 mm²151 A118 A44.94 V (93.62%)3.1 V74.13 V (154.44%)13482.0 WDrop High
70 mm²192 A150 A32.1 V (66.87%)15.9 V52.95 V (110.31%)9630.0 WDrop High
95 mm²232 A181 A23.65 V (49.28%)24.3 V39.02 V (81.28%)7095.8 WDrop High
120 mm²269 A210 A18.72 V (39.01%)29.3 V30.89 V (64.35%)5617.5 WDrop High
150 mm²309 A241 A14.98 V (31.21%)33.0 V24.71 V (51.48%)4494.0 WDrop High
185 mm²353 A275 A12.15 V (25.3%)35.9 V20.04 V (41.74%)3643.8 WDrop High
240 mm²415 A324 A9.36 V (19.51%)38.6 V15.44 V (32.17%)2808.8 WDrop High
300 mm²477 A372 A7.49 V (15.6%)40.5 V12.35 V (25.74%)2247.0 WDrop High
400 mm²570 A445 A5.62 V (11.7%)42.4 V9.27 V (19.3%)1685.2 WDrop High

FAQ — 300 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 300A at 175 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 300A over 175m at 48V (voltage drop: 1.41V or 2.92%).

What is the power capacity of 300A at 48V?

At unity power factor, 300A at 48V supports 14.4 kW with a standard 300A circuit breaker.