⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

300 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 0.43V (0.19%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.44V (0.19%)
Voltage at Load229.6 VLine Loss: 128.4 W
Max Power & Breaker69.0 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A42.8 V (18.61%)187.2 V70.6 V (30.7%)12840.0 WDrop High
2.5 mm²24 A18 A25.68 V (11.17%)204.3 V42.36 V (18.42%)7704.0 WDrop High
4 mm²32 A25 A16.05 V (6.98%)213.9 V26.47 V (11.51%)4815.0 WDrop High
6 mm²41 A32 A10.7 V (4.65%)219.3 V17.65 V (7.67%)3210.0 WDrop High
10 mm²57 A44 A6.42 V (2.79%)223.6 V10.59 V (4.6%)1926.0 WDrop High
16 mm²76 A59 A4.01 V (1.74%)226.0 V6.62 V (2.88%)1203.8 WDrop High
25 mm²101 A78 A2.57 V (1.12%)227.4 V4.24 V (1.84%)770.4 WDrop High
35 mm²125 A97 A1.83 V (0.8%)228.2 V3.03 V (1.32%)550.3 WDrop High
50 mm²151 A118 A1.28 V (0.56%)228.7 V2.12 V (0.92%)385.2 WDrop High
70 mm²192 A150 A0.92 V (0.4%)229.1 V1.51 V (0.66%)275.1 WDrop High
95 mm²232 A181 A0.68 V (0.29%)229.3 V1.11 V (0.48%)202.7 WDrop High
120 mm²269 A210 A0.54 V (0.23%)229.5 V0.88 V (0.38%)160.5 WDrop High
150 mm²309 A241 A0.43 V (0.19%)229.6 V0.71 V (0.31%)128.4 W✓ OK (≤3%)
185 mm²353 A275 A0.35 V (0.15%)229.7 V0.57 V (0.25%)104.1 W✓ OK (≤3%)
240 mm²415 A324 A0.27 V (0.12%)229.7 V0.44 V (0.19%)80.2 W✓ OK (≤3%)
300 mm²477 A372 A0.21 V (0.09%)229.8 V0.35 V (0.15%)64.2 W✓ OK (≤3%)
400 mm²570 A445 A0.16 V (0.07%)229.8 V0.26 V (0.12%)48.1 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 300A at 5 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 5m at 230V (voltage drop: 0.43V or 0.19%).

What is the power capacity of 300A at 230V?

At unity power factor, 300A at 230V supports 69.0 kW with a standard 300A circuit breaker.