32 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 11.86V (2.86%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 12.23V (2.95%)
Voltage at Load403.1 VLine Loss: 657.4 W
Max Power & Breaker23.0 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A79.07 V (19.05%)335.9 V130.43 V (31.43%)4382.7 WDrop High
2.5 mm²24 A18 A47.44 V (11.43%)367.6 V78.26 V (18.86%)2629.6 WDrop High
4 mm²32 A25 A29.65 V (7.15%)385.3 V48.91 V (11.79%)1643.5 WDrop High
6 mm²41 A32 A19.77 V (4.76%)395.2 V32.61 V (7.86%)1095.7 W~ ≤5%
10 mm²57 A44 A11.86 V (2.86%)403.1 V19.57 V (4.71%)657.4 W✓ OK (≤3%)
16 mm²76 A59 A7.41 V (1.79%)407.6 V12.23 V (2.95%)410.9 W✓ OK (≤3%)
25 mm²101 A78 A4.74 V (1.14%)410.3 V7.83 V (1.89%)263.0 W✓ OK (≤3%)
35 mm²125 A97 A3.39 V (0.82%)411.6 V5.59 V (1.35%)187.8 W✓ OK (≤3%)
50 mm²151 A118 A2.37 V (0.57%)412.6 V3.91 V (0.94%)131.5 W✓ OK (≤3%)
70 mm²192 A150 A1.69 V (0.41%)413.3 V2.8 V (0.67%)93.9 W✓ OK (≤3%)
95 mm²232 A181 A1.25 V (0.3%)413.8 V2.06 V (0.5%)69.2 W✓ OK (≤3%)
120 mm²269 A210 A0.99 V (0.24%)414.0 V1.63 V (0.39%)54.8 W✓ OK (≤3%)
150 mm²309 A241 A0.79 V (0.19%)414.2 V1.3 V (0.31%)43.8 W✓ OK (≤3%)
185 mm²353 A275 A0.64 V (0.15%)414.4 V1.06 V (0.25%)35.5 W✓ OK (≤3%)
240 mm²415 A324 A0.49 V (0.12%)414.5 V0.82 V (0.2%)27.4 W✓ OK (≤3%)
300 mm²477 A372 A0.4 V (0.1%)414.6 V0.65 V (0.16%)21.9 W✓ OK (≤3%)
400 mm²570 A445 A0.3 V (0.07%)414.7 V0.49 V (0.12%)16.4 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 32A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 32A over 100m at 415V (voltage drop: 11.86V or 2.86%).

What is the power capacity of 32A at 415V?

At unity power factor, 32A at 415V supports 23.0 kW with a standard 32A circuit breaker.