125 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 10.92V (2.63%)
Voltage at Load405.7 VLine Loss: 2006.2 W
Max Power & Breaker89.85 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A308.88 V (74.43%)106.1 V509.51 V (122.77%)66875.0 WDrop High
2.5 mm²24 A18 A185.33 V (44.66%)229.7 V305.71 V (73.66%)40125.0 WDrop High
4 mm²32 A25 A115.83 V (27.91%)299.2 V191.07 V (46.04%)25078.1 WDrop High
6 mm²41 A32 A77.22 V (18.61%)337.8 V127.38 V (30.69%)16718.8 WDrop High
10 mm²57 A44 A46.33 V (11.16%)368.7 V76.43 V (18.42%)10031.2 WDrop High
16 mm²76 A59 A28.96 V (6.98%)386.0 V47.77 V (11.51%)6269.5 WDrop High
25 mm²101 A78 A18.53 V (4.47%)396.5 V30.57 V (7.37%)4012.5 WDrop High
35 mm²125 A97 A13.24 V (3.19%)401.8 V21.84 V (5.26%)2866.1 W~ ≤5%
50 mm²151 A118 A9.27 V (2.23%)405.7 V15.29 V (3.68%)2006.2 W✓ OK (≤3%)
70 mm²192 A150 A6.62 V (1.59%)408.4 V10.92 V (2.63%)1433.0 W✓ OK (≤3%)
95 mm²232 A181 A4.88 V (1.18%)410.1 V8.04 V (1.94%)1055.9 W✓ OK (≤3%)
120 mm²269 A210 A3.86 V (0.93%)411.1 V6.37 V (1.53%)835.9 W✓ OK (≤3%)
150 mm²309 A241 A3.09 V (0.74%)411.9 V5.1 V (1.23%)668.7 W✓ OK (≤3%)
185 mm²353 A275 A2.5 V (0.6%)412.5 V4.13 V (1.0%)542.2 W✓ OK (≤3%)
240 mm²415 A324 A1.93 V (0.47%)413.1 V3.18 V (0.77%)418.0 W✓ OK (≤3%)
300 mm²477 A372 A1.54 V (0.37%)413.5 V2.55 V (0.61%)334.4 W✓ OK (≤3%)
400 mm²570 A445 A1.16 V (0.28%)413.8 V1.91 V (0.46%)250.8 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 125A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 125A over 100m at 415V (voltage drop: 9.27V or 2.23%).

What is the power capacity of 125A at 415V?

At unity power factor, 125A at 415V supports 89.85 kW with a standard 125A circuit breaker.