10 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 10.19V (2.46%)
Voltage at Load405.7 VLine Loss: 160.5 W
Max Power & Breaker7.19 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.71 V (5.95%)390.3 V40.76 V (9.82%)428.0 WDrop High
2.5 mm²24 A18 A14.83 V (3.57%)400.2 V24.46 V (5.89%)256.8 W~ ≤5%
4 mm²32 A25 A9.27 V (2.23%)405.7 V15.29 V (3.68%)160.5 W✓ OK (≤3%)
6 mm²41 A32 A6.18 V (1.49%)408.8 V10.19 V (2.46%)107.0 W✓ OK (≤3%)
10 mm²57 A44 A3.71 V (0.89%)411.3 V6.11 V (1.47%)64.2 W✓ OK (≤3%)
16 mm²76 A59 A2.32 V (0.56%)412.7 V3.82 V (0.92%)40.1 W✓ OK (≤3%)
25 mm²101 A78 A1.48 V (0.36%)413.5 V2.45 V (0.59%)25.7 W✓ OK (≤3%)
35 mm²125 A97 A1.06 V (0.26%)413.9 V1.75 V (0.42%)18.3 W✓ OK (≤3%)
50 mm²151 A118 A0.74 V (0.18%)414.3 V1.22 V (0.29%)12.8 W✓ OK (≤3%)
70 mm²192 A150 A0.53 V (0.13%)414.5 V0.87 V (0.21%)9.2 W✓ OK (≤3%)
95 mm²232 A181 A0.39 V (0.09%)414.6 V0.64 V (0.16%)6.8 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (0.07%)414.7 V0.51 V (0.12%)5.3 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (0.06%)414.8 V0.41 V (0.1%)4.3 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.05%)414.8 V0.33 V (0.08%)3.5 W✓ OK (≤3%)
240 mm²415 A324 A0.15 V (0.04%)414.8 V0.25 V (0.06%)2.7 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.03%)414.9 V0.2 V (0.05%)2.1 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.02%)414.9 V0.15 V (0.04%)1.6 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 10A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 10A over 100m at 415V (voltage drop: 9.27V or 2.23%).

What is the power capacity of 10A at 415V?

At unity power factor, 10A at 415V supports 7.19 kW with a standard 10A circuit breaker.