32 Amp Cable Size at 30 Meters (230V Single-Phase (IEC Europe / UK / AU))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 30 m (98.4 ft).
Copper Cable (≤3% Drop)6 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 6.78V (2.95%)
Voltage at Load223.2 VLine Loss: 219.1 W
Max Power & Breaker7.36 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 30m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 27.39 V (11.91%) | 202.6 V | 45.18 V (19.65%) | 876.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 16.44 V (7.15%) | 213.6 V | 27.11 V (11.79%) | 525.9 W | Drop High |
| 4 mm² | 32 A | 25 A | 10.27 V (4.47%) | 219.7 V | 16.94 V (7.37%) | 328.7 W | ~ ≤5% |
| 6 mm² | 41 A | 32 A | 6.85 V (2.98%) | 223.2 V | 11.3 V (4.91%) | 219.1 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 4.11 V (1.79%) | 225.9 V | 6.78 V (2.95%) | 131.5 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 2.57 V (1.12%) | 227.4 V | 4.24 V (1.84%) | 82.2 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.64 V (0.71%) | 228.4 V | 2.71 V (1.18%) | 52.6 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.17 V (0.51%) | 228.8 V | 1.94 V (0.84%) | 37.6 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.82 V (0.36%) | 229.2 V | 1.36 V (0.59%) | 26.3 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.59 V (0.26%) | 229.4 V | 0.97 V (0.42%) | 18.8 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.43 V (0.19%) | 229.6 V | 0.71 V (0.31%) | 13.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.34 V (0.15%) | 229.7 V | 0.56 V (0.25%) | 11.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.27 V (0.12%) | 229.7 V | 0.45 V (0.2%) | 8.8 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.22 V (0.1%) | 229.8 V | 0.37 V (0.16%) | 7.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.17 V (0.07%) | 229.8 V | 0.28 V (0.12%) | 5.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.14 V (0.06%) | 229.9 V | 0.23 V (0.1%) | 4.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.1 V (0.04%) | 229.9 V | 0.17 V (0.07%) | 3.3 W | ✓ OK (≤3%) |
FAQ — 32 Amp Cable Size at 30 Meters (230V Single-Phase (IEC Europe / UK / AU))
What mm² cable size is required for 32A at 30 meters (230V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 32A over 30m at 230V (voltage drop: 6.85V or 2.98%).
What is the power capacity of 32A at 230V?
At unity power factor, 32A at 230V supports 7.36 kW with a standard 32A circuit breaker.
Related Lengths & Currents (230V)
32A · 5m (230V)32A · 10m (230V)32A · 15m (230V)32A · 20m (230V)32A · 25m (230V)32A · 35m (230V)32A · 40m (230V)32A · 45m (230V)32A · 50m (230V)32A · 60m (230V)32A · 70m (230V)10A · 30m (230V)16A · 30m (230V)20A · 30m (230V)25A · 30m (230V)40A · 30m (230V)50A · 30m (230V)63A · 30m (230V)80A · 30m (230V)100A · 30m (230V)125A · 30m (230V)160A · 30m (230V)200A · 30m (230V)