325 Amp Cable Size at 100 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 5.8V (2.52%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.74V (2.49%)
Voltage at Load224.2 VLine Loss: 1883.6 W
Max Power & Breaker74.75 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A927.33 V (403.19%)0.0 V1529.67 V (665.07%)301383.3 WDrop High
2.5 mm²24 A18 A556.4 V (241.91%)0.0 V917.8 V (399.04%)180830.0 WDrop High
4 mm²32 A25 A347.75 V (151.2%)0.0 V573.62 V (249.4%)113018.7 WDrop High
6 mm²41 A32 A231.83 V (100.8%)0.0 V382.42 V (166.27%)75345.8 WDrop High
10 mm²57 A44 A139.1 V (60.48%)90.9 V229.45 V (99.76%)45207.5 WDrop High
16 mm²76 A59 A86.94 V (37.8%)143.1 V143.41 V (62.35%)28254.7 WDrop High
25 mm²101 A78 A55.64 V (24.19%)174.4 V91.78 V (39.9%)18083.0 WDrop High
35 mm²125 A97 A39.74 V (17.28%)190.3 V65.56 V (28.5%)12916.4 WDrop High
50 mm²151 A118 A27.82 V (12.1%)202.2 V45.89 V (19.95%)9041.5 WDrop High
70 mm²192 A150 A19.87 V (8.64%)210.1 V32.78 V (14.25%)6458.2 WDrop High
95 mm²232 A181 A14.64 V (6.37%)215.4 V24.15 V (10.5%)4758.7 WDrop High
120 mm²269 A210 A11.59 V (5.04%)218.4 V19.12 V (8.31%)3767.3 WDrop High
150 mm²309 A241 A9.27 V (4.03%)220.7 V15.3 V (6.65%)3013.8 WDrop High
185 mm²353 A275 A7.52 V (3.27%)222.5 V12.4 V (5.39%)2443.6 W~ ≤5%
240 mm²415 A324 A5.8 V (2.52%)224.2 V9.56 V (4.16%)1883.6 W✓ OK (≤3%)
300 mm²477 A372 A4.64 V (2.02%)225.4 V7.65 V (3.33%)1506.9 W✓ OK (≤3%)
400 mm²570 A445 A3.48 V (1.51%)226.5 V5.74 V (2.49%)1130.2 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 100 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 325A at 100 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 325A over 100m at 230V (voltage drop: 5.8V or 2.52%).

What is the power capacity of 325A at 230V?

At unity power factor, 325A at 230V supports 74.75 kW with a standard 350A circuit breaker.