325 Amp Cable Size at 50 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 3.76V (1.63%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 3.82V (1.66%)
Voltage at Load226.2 VLine Loss: 1221.8 W
Max Power & Breaker74.75 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A463.67 V (201.59%)0.0 V764.83 V (332.54%)150691.7 WDrop High
2.5 mm²24 A18 A278.2 V (120.96%)0.0 V458.9 V (199.52%)90415.0 WDrop High
4 mm²32 A25 A173.87 V (75.6%)56.1 V286.81 V (124.7%)56509.4 WDrop High
6 mm²41 A32 A115.92 V (50.4%)114.1 V191.21 V (83.13%)37672.9 WDrop High
10 mm²57 A44 A69.55 V (30.24%)160.5 V114.72 V (49.88%)22603.7 WDrop High
16 mm²76 A59 A43.47 V (18.9%)186.5 V71.7 V (31.18%)14127.3 WDrop High
25 mm²101 A78 A27.82 V (12.1%)202.2 V45.89 V (19.95%)9041.5 WDrop High
35 mm²125 A97 A19.87 V (8.64%)210.1 V32.78 V (14.25%)6458.2 WDrop High
50 mm²151 A118 A13.91 V (6.05%)216.1 V22.95 V (9.98%)4520.7 WDrop High
70 mm²192 A150 A9.94 V (4.32%)220.1 V16.39 V (7.13%)3229.1 WDrop High
95 mm²232 A181 A7.32 V (3.18%)222.7 V12.08 V (5.25%)2379.3 WDrop High
120 mm²269 A210 A5.8 V (2.52%)224.2 V9.56 V (4.16%)1883.6 WDrop High
150 mm²309 A241 A4.64 V (2.02%)225.4 V7.65 V (3.33%)1506.9 WDrop High
185 mm²353 A275 A3.76 V (1.63%)226.2 V6.2 V (2.7%)1221.8 W✓ OK (≤3%)
240 mm²415 A324 A2.9 V (1.26%)227.1 V4.78 V (2.08%)941.8 W✓ OK (≤3%)
300 mm²477 A372 A2.32 V (1.01%)227.7 V3.82 V (1.66%)753.5 W✓ OK (≤3%)
400 mm²570 A445 A1.74 V (0.76%)228.3 V2.87 V (1.25%)565.1 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 50 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 325A at 50 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 50m at 230V (voltage drop: 3.76V or 1.63%).

What is the power capacity of 325A at 230V?

At unity power factor, 325A at 230V supports 74.75 kW with a standard 350A circuit breaker.