325 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.88V (0.82%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.91V (0.83%)
Voltage at Load228.1 VLine Loss: 610.9 W
Max Power & Breaker74.75 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A231.83 V (100.8%)0.0 V382.42 V (166.27%)75345.8 WDrop High
2.5 mm²24 A18 A139.1 V (60.48%)90.9 V229.45 V (99.76%)45207.5 WDrop High
4 mm²32 A25 A86.94 V (37.8%)143.1 V143.41 V (62.35%)28254.7 WDrop High
6 mm²41 A32 A57.96 V (25.2%)172.0 V95.6 V (41.57%)18836.5 WDrop High
10 mm²57 A44 A34.77 V (15.12%)195.2 V57.36 V (24.94%)11301.9 WDrop High
16 mm²76 A59 A21.73 V (9.45%)208.3 V35.85 V (15.59%)7063.7 WDrop High
25 mm²101 A78 A13.91 V (6.05%)216.1 V22.95 V (9.98%)4520.7 WDrop High
35 mm²125 A97 A9.94 V (4.32%)220.1 V16.39 V (7.13%)3229.1 WDrop High
50 mm²151 A118 A6.95 V (3.02%)223.0 V11.47 V (4.99%)2260.4 WDrop High
70 mm²192 A150 A4.97 V (2.16%)225.0 V8.19 V (3.56%)1614.6 WDrop High
95 mm²232 A181 A3.66 V (1.59%)226.3 V6.04 V (2.63%)1189.7 WDrop High
120 mm²269 A210 A2.9 V (1.26%)227.1 V4.78 V (2.08%)941.8 WDrop High
150 mm²309 A241 A2.32 V (1.01%)227.7 V3.82 V (1.66%)753.5 WDrop High
185 mm²353 A275 A1.88 V (0.82%)228.1 V3.1 V (1.35%)610.9 W✓ OK (≤3%)
240 mm²415 A324 A1.45 V (0.63%)228.6 V2.39 V (1.04%)470.9 W✓ OK (≤3%)
300 mm²477 A372 A1.16 V (0.5%)228.8 V1.91 V (0.83%)376.7 W✓ OK (≤3%)
400 mm²570 A445 A0.87 V (0.38%)229.1 V1.43 V (0.62%)282.5 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 325A at 25 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 25m at 230V (voltage drop: 1.88V or 0.82%).

What is the power capacity of 325A at 230V?

At unity power factor, 325A at 230V supports 74.75 kW with a standard 350A circuit breaker.