⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.33V (0.08%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.33V (0.08%)
Voltage at Load399.7 VLine Loss: 183.3 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A40.15 V (10.04%)359.8 V66.24 V (16.56%)22603.8 WDrop High
2.5 mm²24 A18 A24.09 V (6.02%)375.9 V39.74 V (9.94%)13562.2 WDrop High
4 mm²32 A25 A15.06 V (3.76%)384.9 V24.84 V (6.21%)8476.4 WDrop High
6 mm²41 A32 A10.04 V (2.51%)390.0 V16.56 V (4.14%)5650.9 WDrop High
10 mm²57 A44 A6.02 V (1.51%)394.0 V9.94 V (2.48%)3390.6 WDrop High
16 mm²76 A59 A3.76 V (0.94%)396.2 V6.21 V (1.55%)2119.1 WDrop High
25 mm²101 A78 A2.41 V (0.6%)397.6 V3.97 V (0.99%)1356.2 WDrop High
35 mm²125 A97 A1.72 V (0.43%)398.3 V2.84 V (0.71%)968.7 WDrop High
50 mm²151 A118 A1.2 V (0.3%)398.8 V1.99 V (0.5%)678.1 WDrop High
70 mm²192 A150 A0.86 V (0.22%)399.1 V1.42 V (0.35%)484.4 WDrop High
95 mm²232 A181 A0.63 V (0.16%)399.4 V1.05 V (0.26%)356.9 WDrop High
120 mm²269 A210 A0.5 V (0.13%)399.5 V0.83 V (0.21%)282.5 WDrop High
150 mm²309 A241 A0.4 V (0.1%)399.6 V0.66 V (0.17%)226.0 WDrop High
185 mm²353 A275 A0.33 V (0.08%)399.7 V0.54 V (0.13%)183.3 W✓ OK (≤3%)
240 mm²415 A324 A0.25 V (0.06%)399.7 V0.41 V (0.1%)141.3 W✓ OK (≤3%)
300 mm²477 A372 A0.2 V (0.05%)399.8 V0.33 V (0.08%)113.0 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.04%)399.8 V0.25 V (0.06%)84.8 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 325A at 5 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 5m at 400V (voltage drop: 0.33V or 0.08%).

What is the power capacity of 325A at 400V?

At unity power factor, 325A at 400V supports 225.17 kW with a standard 350A circuit breaker.