⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 60 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 3.91V (0.98%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 3.97V (0.99%)
Voltage at Load396.1 VLine Loss: 2199.3 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A481.86 V (120.46%)0.0 V794.84 V (198.71%)271245.0 WDrop High
2.5 mm²24 A18 A289.11 V (72.28%)110.9 V476.9 V (119.23%)162747.0 WDrop High
4 mm²32 A25 A180.7 V (45.17%)219.3 V298.06 V (74.52%)101716.9 WDrop High
6 mm²41 A32 A120.46 V (30.12%)279.5 V198.71 V (49.68%)67811.2 WDrop High
10 mm²57 A44 A72.28 V (18.07%)327.7 V119.23 V (29.81%)40686.8 WDrop High
16 mm²76 A59 A45.17 V (11.29%)354.8 V74.52 V (18.63%)25429.2 WDrop High
25 mm²101 A78 A28.91 V (7.23%)371.1 V47.69 V (11.92%)16274.7 WDrop High
35 mm²125 A97 A20.65 V (5.16%)379.3 V34.06 V (8.52%)11624.8 WDrop High
50 mm²151 A118 A14.46 V (3.61%)385.5 V23.85 V (5.96%)8137.4 WDrop High
70 mm²192 A150 A10.33 V (2.58%)389.7 V17.03 V (4.26%)5812.4 WDrop High
95 mm²232 A181 A7.61 V (1.9%)392.4 V12.55 V (3.14%)4282.8 WDrop High
120 mm²269 A210 A6.02 V (1.51%)394.0 V9.94 V (2.48%)3390.6 WDrop High
150 mm²309 A241 A4.82 V (1.2%)395.2 V7.95 V (1.99%)2712.4 WDrop High
185 mm²353 A275 A3.91 V (0.98%)396.1 V6.44 V (1.61%)2199.3 W✓ OK (≤3%)
240 mm²415 A324 A3.01 V (0.75%)397.0 V4.97 V (1.24%)1695.3 W✓ OK (≤3%)
300 mm²477 A372 A2.41 V (0.6%)397.6 V3.97 V (0.99%)1356.2 W✓ OK (≤3%)
400 mm²570 A445 A1.81 V (0.45%)398.2 V2.98 V (0.75%)1017.2 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 60 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 325A at 60 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 60m at 400V (voltage drop: 3.91V or 0.98%).

What is the power capacity of 325A at 400V?

At unity power factor, 325A at 400V supports 225.17 kW with a standard 350A circuit breaker.