325 Amp Cable Size at 40 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 2.6V (0.65%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 2.65V (0.66%)
Voltage at Load397.4 VLine Loss: 1466.2 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A321.24 V (80.31%)78.8 V529.89 V (132.47%)180830.0 WDrop High
2.5 mm²24 A18 A192.74 V (48.19%)207.3 V317.94 V (79.48%)108498.0 WDrop High
4 mm²32 A25 A120.46 V (30.12%)279.5 V198.71 V (49.68%)67811.2 WDrop High
6 mm²41 A32 A80.31 V (20.08%)319.7 V132.47 V (33.12%)45207.5 WDrop High
10 mm²57 A44 A48.19 V (12.05%)351.8 V79.48 V (19.87%)27124.5 WDrop High
16 mm²76 A59 A30.12 V (7.53%)369.9 V49.68 V (12.42%)16952.8 WDrop High
25 mm²101 A78 A19.27 V (4.82%)380.7 V31.79 V (7.95%)10849.8 WDrop High
35 mm²125 A97 A13.77 V (3.44%)386.2 V22.71 V (5.68%)7749.9 WDrop High
50 mm²151 A118 A9.64 V (2.41%)390.4 V15.9 V (3.97%)5424.9 WDrop High
70 mm²192 A150 A6.88 V (1.72%)393.1 V11.35 V (2.84%)3874.9 WDrop High
95 mm²232 A181 A5.07 V (1.27%)394.9 V8.37 V (2.09%)2855.2 WDrop High
120 mm²269 A210 A4.02 V (1.0%)396.0 V6.62 V (1.66%)2260.4 WDrop High
150 mm²309 A241 A3.21 V (0.8%)396.8 V5.3 V (1.32%)1808.3 WDrop High
185 mm²353 A275 A2.6 V (0.65%)397.4 V4.3 V (1.07%)1466.2 W✓ OK (≤3%)
240 mm²415 A324 A2.01 V (0.5%)398.0 V3.31 V (0.83%)1130.2 W✓ OK (≤3%)
300 mm²477 A372 A1.61 V (0.4%)398.4 V2.65 V (0.66%)904.1 W✓ OK (≤3%)
400 mm²570 A445 A1.2 V (0.3%)398.8 V1.99 V (0.5%)678.1 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 40 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 325A at 40 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 40m at 400V (voltage drop: 2.6V or 0.65%).

What is the power capacity of 325A at 400V?

At unity power factor, 325A at 400V supports 225.17 kW with a standard 350A circuit breaker.