⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

35 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 15.57V (2.26%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 16.05V (2.33%)
Voltage at Load674.4 VLine Loss: 943.7 W
Max Power & Breaker41.83 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A103.78 V (15.04%)586.2 V171.2 V (24.81%)6291.6 WDrop High
2.5 mm²24 A18 A62.27 V (9.02%)627.7 V102.72 V (14.89%)3775.0 WDrop High
4 mm²32 A25 A38.92 V (5.64%)651.1 V64.2 V (9.3%)2359.3 WDrop High
6 mm²41 A32 A25.95 V (3.76%)664.1 V42.8 V (6.2%)1572.9 W~ ≤5%
10 mm²57 A44 A15.57 V (2.26%)674.4 V25.68 V (3.72%)943.7 W✓ OK (≤3%)
16 mm²76 A59 A9.73 V (1.41%)680.3 V16.05 V (2.33%)589.8 W✓ OK (≤3%)
25 mm²101 A78 A6.23 V (0.9%)683.8 V10.27 V (1.49%)377.5 W✓ OK (≤3%)
35 mm²125 A97 A4.45 V (0.64%)685.6 V7.34 V (1.06%)269.6 W✓ OK (≤3%)
50 mm²151 A118 A3.11 V (0.45%)686.9 V5.14 V (0.74%)188.7 W✓ OK (≤3%)
70 mm²192 A150 A2.22 V (0.32%)687.8 V3.67 V (0.53%)134.8 W✓ OK (≤3%)
95 mm²232 A181 A1.64 V (0.24%)688.4 V2.7 V (0.39%)99.3 W✓ OK (≤3%)
120 mm²269 A210 A1.3 V (0.19%)688.7 V2.14 V (0.31%)78.6 W✓ OK (≤3%)
150 mm²309 A241 A1.04 V (0.15%)689.0 V1.71 V (0.25%)62.9 W✓ OK (≤3%)
185 mm²353 A275 A0.84 V (0.12%)689.2 V1.39 V (0.2%)51.0 W✓ OK (≤3%)
240 mm²415 A324 A0.65 V (0.09%)689.4 V1.07 V (0.16%)39.3 W✓ OK (≤3%)
300 mm²477 A372 A0.52 V (0.08%)689.5 V0.86 V (0.12%)31.5 W✓ OK (≤3%)
400 mm²570 A445 A0.39 V (0.06%)689.6 V0.64 V (0.09%)23.6 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 35A at 120 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 35A over 120m at 690V (voltage drop: 15.57V or 2.26%).

What is the power capacity of 35A at 690V?

At unity power factor, 35A at 690V supports 41.83 kW with a standard 35A circuit breaker.