35 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 50 m (164.0 ft).
Copper Cable (≤3% Drop)6 mm²Drop: 10.81V (1.57%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 10.7V (1.55%)
Voltage at Load679.2 VLine Loss: 655.4 W
Max Power & Breaker41.83 kW35A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 50m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 43.24 V (6.27%) | 646.8 V | 71.33 V (10.34%) | 2621.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 25.95 V (3.76%) | 664.1 V | 42.8 V (6.2%) | 1572.9 W | Drop High |
| 4 mm² | 32 A | 25 A | 16.22 V (2.35%) | 673.8 V | 26.75 V (3.88%) | 983.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 10.81 V (1.57%) | 679.2 V | 17.83 V (2.58%) | 655.4 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 6.49 V (0.94%) | 683.5 V | 10.7 V (1.55%) | 393.2 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 4.05 V (0.59%) | 685.9 V | 6.69 V (0.97%) | 245.8 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 2.59 V (0.38%) | 687.4 V | 4.28 V (0.62%) | 157.3 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.85 V (0.27%) | 688.1 V | 3.06 V (0.44%) | 112.3 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.3 V (0.19%) | 688.7 V | 2.14 V (0.31%) | 78.6 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.93 V (0.13%) | 689.1 V | 1.53 V (0.22%) | 56.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.68 V (0.1%) | 689.3 V | 1.13 V (0.16%) | 41.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.54 V (0.08%) | 689.5 V | 0.89 V (0.13%) | 32.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.43 V (0.06%) | 689.6 V | 0.71 V (0.1%) | 26.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.35 V (0.05%) | 689.6 V | 0.58 V (0.08%) | 21.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.27 V (0.04%) | 689.7 V | 0.45 V (0.06%) | 16.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.22 V (0.03%) | 689.8 V | 0.36 V (0.05%) | 13.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.16 V (0.02%) | 689.8 V | 0.27 V (0.04%) | 9.8 W | ✓ OK (≤3%) |
FAQ — 35 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 35A at 50 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 35A over 50m at 690V (voltage drop: 10.81V or 1.57%).
What is the power capacity of 35A at 690V?
At unity power factor, 35A at 690V supports 41.83 kW with a standard 35A circuit breaker.
Related Lengths & Currents (690V)
35A · 5m (690V)35A · 10m (690V)35A · 15m (690V)35A · 20m (690V)35A · 25m (690V)35A · 30m (690V)35A · 35m (690V)35A · 40m (690V)35A · 45m (690V)35A · 60m (690V)35A · 70m (690V)10A · 50m (690V)16A · 50m (690V)20A · 50m (690V)25A · 50m (690V)32A · 50m (690V)40A · 50m (690V)50A · 50m (690V)63A · 50m (690V)80A · 50m (690V)100A · 50m (690V)125A · 50m (690V)160A · 50m (690V)200A · 50m (690V)