35 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.42V (2.95%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.08V (2.25%)
Voltage at Load46.6 VLine Loss: 49.6 W
Max Power & Breaker1.68 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A174.77 V (364.1%)0.0 V288.28 V (600.59%)6116.8 WDrop High
2.5 mm²24 A18 A104.86 V (218.46%)0.0 V172.97 V (360.35%)3670.1 WDrop High
4 mm²32 A25 A65.54 V (136.54%)0.0 V108.11 V (225.22%)2293.8 WDrop High
6 mm²41 A32 A43.69 V (91.02%)4.3 V72.07 V (150.15%)1529.2 WDrop High
10 mm²57 A44 A26.21 V (54.61%)21.8 V43.24 V (90.09%)917.5 WDrop High
16 mm²76 A59 A16.38 V (34.13%)31.6 V27.03 V (56.31%)573.5 WDrop High
25 mm²101 A78 A10.49 V (21.85%)37.5 V17.3 V (36.04%)367.0 WDrop High
35 mm²125 A97 A7.49 V (15.6%)40.5 V12.35 V (25.74%)262.1 WDrop High
50 mm²151 A118 A5.24 V (10.92%)42.8 V8.65 V (18.02%)183.5 WDrop High
70 mm²192 A150 A3.74 V (7.8%)44.3 V6.18 V (12.87%)131.1 WDrop High
95 mm²232 A181 A2.76 V (5.75%)45.2 V4.55 V (9.48%)96.6 WDrop High
120 mm²269 A210 A2.18 V (4.55%)45.8 V3.6 V (7.51%)76.5 W~ ≤5%
150 mm²309 A241 A1.75 V (3.64%)46.3 V2.88 V (6.01%)61.2 W~ ≤5%
185 mm²353 A275 A1.42 V (2.95%)46.6 V2.34 V (4.87%)49.6 W✓ OK (≤3%)
240 mm²415 A324 A1.09 V (2.28%)46.9 V1.8 V (3.75%)38.2 W✓ OK (≤3%)
300 mm²477 A372 A0.87 V (1.82%)47.1 V1.44 V (3.0%)30.6 W✓ OK (≤3%)
400 mm²570 A445 A0.66 V (1.37%)47.3 V1.08 V (2.25%)22.9 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 35A at 175 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 35A over 175m at 48V (voltage drop: 1.42V or 2.95%).

What is the power capacity of 35A at 48V?

At unity power factor, 35A at 48V supports 1.68 kW with a standard 35A circuit breaker.