35 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 1.05V (2.18%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.24V (2.57%)
Voltage at Load47.0 VLine Loss: 36.7 W
Max Power & Breaker1.68 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A34.95 V (72.82%)13.0 V57.66 V (120.12%)1223.4 WDrop High
2.5 mm²24 A18 A20.97 V (43.69%)27.0 V34.59 V (72.07%)734.0 WDrop High
4 mm²32 A25 A13.11 V (27.31%)34.9 V21.62 V (45.04%)458.8 WDrop High
6 mm²41 A32 A8.74 V (18.2%)39.3 V14.41 V (30.03%)305.8 WDrop High
10 mm²57 A44 A5.24 V (10.92%)42.8 V8.65 V (18.02%)183.5 WDrop High
16 mm²76 A59 A3.28 V (6.83%)44.7 V5.41 V (11.26%)114.7 WDrop High
25 mm²101 A78 A2.1 V (4.37%)45.9 V3.46 V (7.21%)73.4 W~ ≤5%
35 mm²125 A97 A1.5 V (3.12%)46.5 V2.47 V (5.15%)52.4 W~ ≤5%
50 mm²151 A118 A1.05 V (2.18%)47.0 V1.73 V (3.6%)36.7 W✓ OK (≤3%)
70 mm²192 A150 A0.75 V (1.56%)47.3 V1.24 V (2.57%)26.2 W✓ OK (≤3%)
95 mm²232 A181 A0.55 V (1.15%)47.4 V0.91 V (1.9%)19.3 W✓ OK (≤3%)
120 mm²269 A210 A0.44 V (0.91%)47.6 V0.72 V (1.5%)15.3 W✓ OK (≤3%)
150 mm²309 A241 A0.35 V (0.73%)47.7 V0.58 V (1.2%)12.2 W✓ OK (≤3%)
185 mm²353 A275 A0.28 V (0.59%)47.7 V0.47 V (0.97%)9.9 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.46%)47.8 V0.36 V (0.75%)7.6 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.36%)47.8 V0.29 V (0.6%)6.1 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.27%)47.9 V0.22 V (0.45%)4.6 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 35A at 35 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 35A over 35m at 48V (voltage drop: 1.05V or 2.18%).

What is the power capacity of 35A at 48V?

At unity power factor, 35A at 48V supports 1.68 kW with a standard 35A circuit breaker.