35 Amp Cable Size at 35 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 7.57V (1.82%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 7.49V (1.8%)
Voltage at Load407.4 VLine Loss: 458.8 W
Max Power & Breaker25.16 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A30.27 V (7.29%)384.7 V49.93 V (12.03%)1835.0 WDrop High
2.5 mm²24 A18 A18.16 V (4.38%)396.8 V29.96 V (7.22%)1101.0 WDrop High
4 mm²32 A25 A11.35 V (2.74%)403.6 V18.72 V (4.51%)688.1 WDrop High
6 mm²41 A32 A7.57 V (1.82%)407.4 V12.48 V (3.01%)458.8 W✓ OK (≤3%)
10 mm²57 A44 A4.54 V (1.09%)410.5 V7.49 V (1.8%)275.3 W✓ OK (≤3%)
16 mm²76 A59 A2.84 V (0.68%)412.2 V4.68 V (1.13%)172.0 W✓ OK (≤3%)
25 mm²101 A78 A1.82 V (0.44%)413.2 V3.0 V (0.72%)110.1 W✓ OK (≤3%)
35 mm²125 A97 A1.3 V (0.31%)413.7 V2.14 V (0.52%)78.6 W✓ OK (≤3%)
50 mm²151 A118 A0.91 V (0.22%)414.1 V1.5 V (0.36%)55.1 W✓ OK (≤3%)
70 mm²192 A150 A0.65 V (0.16%)414.4 V1.07 V (0.26%)39.3 W✓ OK (≤3%)
95 mm²232 A181 A0.48 V (0.12%)414.5 V0.79 V (0.19%)29.0 W✓ OK (≤3%)
120 mm²269 A210 A0.38 V (0.09%)414.6 V0.62 V (0.15%)22.9 W✓ OK (≤3%)
150 mm²309 A241 A0.3 V (0.07%)414.7 V0.5 V (0.12%)18.4 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.06%)414.8 V0.4 V (0.1%)14.9 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.05%)414.8 V0.31 V (0.08%)11.5 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.04%)414.8 V0.25 V (0.06%)9.2 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.03%)414.9 V0.19 V (0.05%)6.9 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 35 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 35A at 35 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 35A over 35m at 415V (voltage drop: 7.57V or 1.82%).

What is the power capacity of 35A at 415V?

At unity power factor, 35A at 415V supports 25.16 kW with a standard 35A circuit breaker.