35 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 40 m (131.2 ft).
Copper Cable (≤3% Drop)6 mm²Drop: 8.65V (2.08%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 8.56V (2.06%)
Voltage at Load406.4 VLine Loss: 524.3 W
Max Power & Breaker25.16 kW35A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 40m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 34.59 V (8.34%) | 380.4 V | 57.07 V (13.75%) | 2097.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 20.76 V (5.0%) | 394.2 V | 34.24 V (8.25%) | 1258.3 W | Drop High |
| 4 mm² | 32 A | 25 A | 12.97 V (3.13%) | 402.0 V | 21.4 V (5.16%) | 786.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 8.65 V (2.08%) | 406.4 V | 14.27 V (3.44%) | 524.3 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 5.19 V (1.25%) | 409.8 V | 8.56 V (2.06%) | 314.6 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 3.24 V (0.78%) | 411.8 V | 5.35 V (1.29%) | 196.6 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 2.08 V (0.5%) | 412.9 V | 3.42 V (0.83%) | 125.8 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.48 V (0.36%) | 413.5 V | 2.45 V (0.59%) | 89.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.04 V (0.25%) | 414.0 V | 1.71 V (0.41%) | 62.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.74 V (0.18%) | 414.3 V | 1.22 V (0.29%) | 44.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.55 V (0.13%) | 414.5 V | 0.9 V (0.22%) | 33.1 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.43 V (0.1%) | 414.6 V | 0.71 V (0.17%) | 26.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.35 V (0.08%) | 414.7 V | 0.57 V (0.14%) | 21.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.28 V (0.07%) | 414.7 V | 0.46 V (0.11%) | 17.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.22 V (0.05%) | 414.8 V | 0.36 V (0.09%) | 13.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.17 V (0.04%) | 414.8 V | 0.29 V (0.07%) | 10.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.13 V (0.03%) | 414.9 V | 0.21 V (0.05%) | 7.9 W | ✓ OK (≤3%) |
FAQ — 35 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 35A at 40 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 35A over 40m at 415V (voltage drop: 8.65V or 2.08%).
What is the power capacity of 35A at 415V?
At unity power factor, 35A at 415V supports 25.16 kW with a standard 35A circuit breaker.
Related Lengths & Currents (415V)
35A · 5m (415V)35A · 10m (415V)35A · 15m (415V)35A · 20m (415V)35A · 25m (415V)35A · 30m (415V)35A · 35m (415V)35A · 45m (415V)35A · 50m (415V)35A · 60m (415V)35A · 70m (415V)10A · 40m (415V)16A · 40m (415V)20A · 40m (415V)25A · 40m (415V)32A · 40m (415V)40A · 40m (415V)50A · 40m (415V)63A · 40m (415V)80A · 40m (415V)100A · 40m (415V)125A · 40m (415V)160A · 40m (415V)200A · 40m (415V)