80 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 35 m (114.8 ft).
Copper Cable (≤3% Drop)95 mm²Drop: 1.26V (2.63%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 1.32V (2.75%)
Voltage at Load46.7 VLine Loss: 100.9 W
Max Power & Breaker3.84 kW80A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 79.89 V (166.44%) | 0.0 V | 131.79 V (274.56%) | 6391.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 47.94 V (99.87%) | 0.1 V | 79.07 V (164.73%) | 3834.9 W | Drop High |
| 4 mm² | 32 A | 25 A | 29.96 V (62.42%) | 18.0 V | 49.42 V (102.96%) | 2396.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 19.97 V (41.61%) | 28.0 V | 32.95 V (68.64%) | 1597.9 W | Drop High |
| 10 mm² | 57 A | 44 A | 11.98 V (24.97%) | 36.0 V | 19.77 V (41.18%) | 958.7 W | Drop High |
| 16 mm² | 76 A | 59 A | 7.49 V (15.6%) | 40.5 V | 12.36 V (25.74%) | 599.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 4.79 V (9.99%) | 43.2 V | 7.91 V (16.47%) | 383.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 3.42 V (7.13%) | 44.6 V | 5.65 V (11.77%) | 273.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 2.4 V (4.99%) | 45.6 V | 3.95 V (8.24%) | 191.7 W | ~ ≤5% |
| 70 mm² | 192 A | 150 A | 1.71 V (3.57%) | 46.3 V | 2.82 V (5.88%) | 137.0 W | ~ ≤5% |
| 95 mm² | 232 A | 181 A | 1.26 V (2.63%) | 46.7 V | 2.08 V (4.34%) | 100.9 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.0 V (2.08%) | 47.0 V | 1.65 V (3.43%) | 79.9 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.8 V (1.66%) | 47.2 V | 1.32 V (2.75%) | 63.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.65 V (1.35%) | 47.4 V | 1.07 V (2.23%) | 51.8 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.5 V (1.04%) | 47.5 V | 0.82 V (1.72%) | 39.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.4 V (0.83%) | 47.6 V | 0.66 V (1.37%) | 32.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.3 V (0.62%) | 47.7 V | 0.49 V (1.03%) | 24.0 W | ✓ OK (≤3%) |
FAQ — 80 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
What mm² cable size is required for 80A at 35 meters (48V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 80A over 35m at 48V (voltage drop: 1.26V or 2.63%).
What is the power capacity of 80A at 48V?
At unity power factor, 80A at 48V supports 3.84 kW with a standard 80A circuit breaker.
Related Lengths & Currents (48V)
80A · 5m (48V)80A · 10m (48V)80A · 15m (48V)80A · 20m (48V)80A · 25m (48V)80A · 30m (48V)80A · 40m (48V)80A · 45m (48V)80A · 50m (48V)80A · 60m (48V)80A · 70m (48V)10A · 35m (48V)16A · 35m (48V)20A · 35m (48V)25A · 35m (48V)32A · 35m (48V)40A · 35m (48V)50A · 35m (48V)63A · 35m (48V)100A · 35m (48V)125A · 35m (48V)160A · 35m (48V)200A · 35m (48V)