25 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 1.07V (2.23%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 1.24V (2.57%)
Voltage at Load46.9 VLine Loss: 26.8 W
Max Power & Breaker1.2 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.97 V (52.01%)23.0 V41.18 V (85.8%)624.2 WDrop High
2.5 mm²24 A18 A14.98 V (31.21%)33.0 V24.71 V (51.48%)374.5 WDrop High
4 mm²32 A25 A9.36 V (19.51%)38.6 V15.44 V (32.17%)234.1 WDrop High
6 mm²41 A32 A6.24 V (13.0%)41.8 V10.3 V (21.45%)156.0 WDrop High
10 mm²57 A44 A3.74 V (7.8%)44.3 V6.18 V (12.87%)93.6 WDrop High
16 mm²76 A59 A2.34 V (4.88%)45.7 V3.86 V (8.04%)58.5 W~ ≤5%
25 mm²101 A78 A1.5 V (3.12%)46.5 V2.47 V (5.15%)37.5 W~ ≤5%
35 mm²125 A97 A1.07 V (2.23%)46.9 V1.76 V (3.68%)26.8 W✓ OK (≤3%)
50 mm²151 A118 A0.75 V (1.56%)47.3 V1.24 V (2.57%)18.7 W✓ OK (≤3%)
70 mm²192 A150 A0.53 V (1.11%)47.5 V0.88 V (1.84%)13.4 W✓ OK (≤3%)
95 mm²232 A181 A0.39 V (0.82%)47.6 V0.65 V (1.35%)9.9 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (0.65%)47.7 V0.51 V (1.07%)7.8 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (0.52%)47.8 V0.41 V (0.86%)6.2 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.42%)47.8 V0.33 V (0.7%)5.1 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.33%)47.8 V0.26 V (0.54%)3.9 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.26%)47.9 V0.21 V (0.43%)3.1 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.2%)47.9 V0.15 V (0.32%)2.3 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 25A at 35 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 25A over 35m at 48V (voltage drop: 1.07V or 2.23%).

What is the power capacity of 25A at 48V?

At unity power factor, 25A at 48V supports 1.2 kW with a standard 25A circuit breaker.