35 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 0.47V (1.95%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 0.49V (2.06%)
Voltage at Load23.5 VLine Loss: 16.4 W
Max Power & Breaker0.84 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.99 V (20.81%)19.0 V8.24 V (34.32%)174.8 WDrop High
2.5 mm²24 A18 A3.0 V (12.48%)21.0 V4.94 V (20.59%)104.9 WDrop High
4 mm²32 A25 A1.87 V (7.8%)22.1 V3.09 V (12.87%)65.5 WDrop High
6 mm²41 A32 A1.25 V (5.2%)22.8 V2.06 V (8.58%)43.7 WDrop High
10 mm²57 A44 A0.75 V (3.12%)23.3 V1.24 V (5.15%)26.2 W~ ≤5%
16 mm²76 A59 A0.47 V (1.95%)23.5 V0.77 V (3.22%)16.4 W✓ OK (≤3%)
25 mm²101 A78 A0.3 V (1.25%)23.7 V0.49 V (2.06%)10.5 W✓ OK (≤3%)
35 mm²125 A97 A0.21 V (0.89%)23.8 V0.35 V (1.47%)7.5 W✓ OK (≤3%)
50 mm²151 A118 A0.15 V (0.62%)23.9 V0.25 V (1.03%)5.2 W✓ OK (≤3%)
70 mm²192 A150 A0.11 V (0.45%)23.9 V0.18 V (0.74%)3.7 W✓ OK (≤3%)
95 mm²232 A181 A0.08 V (0.33%)23.9 V0.13 V (0.54%)2.8 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.26%)23.9 V0.1 V (0.43%)2.2 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.21%)24.0 V0.08 V (0.34%)1.7 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.17%)24.0 V0.07 V (0.28%)1.4 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.13%)24.0 V0.05 V (0.21%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.1%)24.0 V0.04 V (0.17%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.08%)24.0 V0.03 V (0.13%)0.7 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 35A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 35A over 5m at 24V (voltage drop: 0.47V or 1.95%).

What is the power capacity of 35A at 24V?

At unity power factor, 35A at 24V supports 0.84 kW with a standard 35A circuit breaker.