35 Amp Cable Size at 35 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 0.55V (2.3%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 0.58V (2.4%)
Voltage at Load23.4 VLine Loss: 19.3 W
Max Power & Breaker0.84 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A34.95 V (145.64%)0.0 V57.66 V (240.24%)1223.4 WDrop High
2.5 mm²24 A18 A20.97 V (87.38%)3.0 V34.59 V (144.14%)734.0 WDrop High
4 mm²32 A25 A13.11 V (54.61%)10.9 V21.62 V (90.09%)458.8 WDrop High
6 mm²41 A32 A8.74 V (36.41%)15.3 V14.41 V (60.06%)305.8 WDrop High
10 mm²57 A44 A5.24 V (21.85%)18.8 V8.65 V (36.04%)183.5 WDrop High
16 mm²76 A59 A3.28 V (13.65%)20.7 V5.41 V (22.52%)114.7 WDrop High
25 mm²101 A78 A2.1 V (8.74%)21.9 V3.46 V (14.41%)73.4 WDrop High
35 mm²125 A97 A1.5 V (6.24%)22.5 V2.47 V (10.3%)52.4 WDrop High
50 mm²151 A118 A1.05 V (4.37%)23.0 V1.73 V (7.21%)36.7 W~ ≤5%
70 mm²192 A150 A0.75 V (3.12%)23.3 V1.24 V (5.15%)26.2 W~ ≤5%
95 mm²232 A181 A0.55 V (2.3%)23.4 V0.91 V (3.79%)19.3 W✓ OK (≤3%)
120 mm²269 A210 A0.44 V (1.82%)23.6 V0.72 V (3.0%)15.3 W✓ OK (≤3%)
150 mm²309 A241 A0.35 V (1.46%)23.7 V0.58 V (2.4%)12.2 W✓ OK (≤3%)
185 mm²353 A275 A0.28 V (1.18%)23.7 V0.47 V (1.95%)9.9 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.91%)23.8 V0.36 V (1.5%)7.6 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.73%)23.8 V0.29 V (1.2%)6.1 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.55%)23.9 V0.22 V (0.9%)4.6 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 35 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 35A at 35 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 35A over 35m at 24V (voltage drop: 0.55V or 2.3%).

What is the power capacity of 35A at 24V?

At unity power factor, 35A at 24V supports 0.84 kW with a standard 35A circuit breaker.