350 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 16.22V (2.35%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.05V (2.33%)
Voltage at Load673.8 VLine Loss: 9830.6 W
Max Power & Breaker418.29 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2594.61 V (376.03%)0.0 V4279.9 V (620.28%)1572900.0 WDrop High
2.5 mm²24 A18 A1556.77 V (225.62%)0.0 V2567.94 V (372.17%)943740.0 WDrop High
4 mm²32 A25 A972.98 V (141.01%)0.0 V1604.96 V (232.6%)589837.5 WDrop High
6 mm²41 A32 A648.65 V (94.01%)41.3 V1069.97 V (155.07%)393225.0 WDrop High
10 mm²57 A44 A389.19 V (56.4%)300.8 V641.98 V (93.04%)235935.0 WDrop High
16 mm²76 A59 A243.24 V (35.25%)446.8 V401.24 V (58.15%)147459.4 WDrop High
25 mm²101 A78 A155.68 V (22.56%)534.3 V256.79 V (37.22%)94374.0 WDrop High
35 mm²125 A97 A111.2 V (16.12%)578.8 V183.42 V (26.58%)67410.0 WDrop High
50 mm²151 A118 A77.84 V (11.28%)612.2 V128.4 V (18.61%)47187.0 WDrop High
70 mm²192 A150 A55.6 V (8.06%)634.4 V91.71 V (13.29%)33705.0 WDrop High
95 mm²232 A181 A40.97 V (5.94%)649.0 V67.58 V (9.79%)24835.3 WDrop High
120 mm²269 A210 A32.43 V (4.7%)657.6 V53.5 V (7.75%)19661.2 WDrop High
150 mm²309 A241 A25.95 V (3.76%)664.1 V42.8 V (6.2%)15729.0 WDrop High
185 mm²353 A275 A21.04 V (3.05%)669.0 V34.7 V (5.03%)12753.2 W~ ≤5%
240 mm²415 A324 A16.22 V (2.35%)673.8 V26.75 V (3.88%)9830.6 W✓ OK (≤3%)
300 mm²477 A372 A12.97 V (1.88%)677.0 V21.4 V (3.1%)7864.5 W✓ OK (≤3%)
400 mm²570 A445 A9.73 V (1.41%)680.3 V16.05 V (2.33%)5898.4 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 350A at 300 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 350A over 300m at 690V (voltage drop: 16.22V or 2.35%).

What is the power capacity of 350A at 690V?

At unity power factor, 350A at 690V supports 418.29 kW with a standard 350A circuit breaker.