125 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 19.86V (2.88%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 19.11V (2.77%)
Voltage at Load670.1 VLine Loss: 4299.1 W
Max Power & Breaker149.39 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A926.65 V (134.3%)0.0 V1528.53 V (221.53%)200625.0 WDrop High
2.5 mm²24 A18 A555.99 V (80.58%)134.0 V917.12 V (132.92%)120375.0 WDrop High
4 mm²32 A25 A347.49 V (50.36%)342.5 V573.2 V (83.07%)75234.4 WDrop High
6 mm²41 A32 A231.66 V (33.57%)458.3 V382.13 V (55.38%)50156.2 WDrop High
10 mm²57 A44 A139.0 V (20.14%)551.0 V229.28 V (33.23%)30093.8 WDrop High
16 mm²76 A59 A86.87 V (12.59%)603.1 V143.3 V (20.77%)18808.6 WDrop High
25 mm²101 A78 A55.6 V (8.06%)634.4 V91.71 V (13.29%)12037.5 WDrop High
35 mm²125 A97 A39.71 V (5.76%)650.3 V65.51 V (9.49%)8598.2 WDrop High
50 mm²151 A118 A27.8 V (4.03%)662.2 V45.86 V (6.65%)6018.7 W~ ≤5%
70 mm²192 A150 A19.86 V (2.88%)670.1 V32.75 V (4.75%)4299.1 W✓ OK (≤3%)
95 mm²232 A181 A14.63 V (2.12%)675.4 V24.13 V (3.5%)3167.8 W✓ OK (≤3%)
120 mm²269 A210 A11.58 V (1.68%)678.4 V19.11 V (2.77%)2507.8 W✓ OK (≤3%)
150 mm²309 A241 A9.27 V (1.34%)680.7 V15.29 V (2.22%)2006.2 W✓ OK (≤3%)
185 mm²353 A275 A7.51 V (1.09%)682.5 V12.39 V (1.8%)1626.7 W✓ OK (≤3%)
240 mm²415 A324 A5.79 V (0.84%)684.2 V9.55 V (1.38%)1253.9 W✓ OK (≤3%)
300 mm²477 A372 A4.63 V (0.67%)685.4 V7.64 V (1.11%)1003.1 W✓ OK (≤3%)
400 mm²570 A445 A3.47 V (0.5%)686.5 V5.73 V (0.83%)752.3 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 125A at 300 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 125A over 300m at 690V (voltage drop: 19.86V or 2.88%).

What is the power capacity of 125A at 690V?

At unity power factor, 125A at 690V supports 149.39 kW with a standard 125A circuit breaker.