100 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 15.89V (2.3%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 19.31V (2.8%)
Voltage at Load674.1 VLine Loss: 2751.4 W
Max Power & Breaker119.51 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A741.32 V (107.44%)0.0 V1222.83 V (177.22%)128400.0 WDrop High
2.5 mm²24 A18 A444.79 V (64.46%)245.2 V733.7 V (106.33%)77040.0 WDrop High
4 mm²32 A25 A277.99 V (40.29%)412.0 V458.56 V (66.46%)48150.0 WDrop High
6 mm²41 A32 A185.33 V (26.86%)504.7 V305.71 V (44.31%)32100.0 WDrop High
10 mm²57 A44 A111.2 V (16.12%)578.8 V183.42 V (26.58%)19260.0 WDrop High
16 mm²76 A59 A69.5 V (10.07%)620.5 V114.64 V (16.61%)12037.5 WDrop High
25 mm²101 A78 A44.48 V (6.45%)645.5 V73.37 V (10.63%)7704.0 WDrop High
35 mm²125 A97 A31.77 V (4.6%)658.2 V52.41 V (7.6%)5502.9 W~ ≤5%
50 mm²151 A118 A22.24 V (3.22%)667.8 V36.68 V (5.32%)3852.0 W~ ≤5%
70 mm²192 A150 A15.89 V (2.3%)674.1 V26.2 V (3.8%)2751.4 W✓ OK (≤3%)
95 mm²232 A181 A11.71 V (1.7%)678.3 V19.31 V (2.8%)2027.4 W✓ OK (≤3%)
120 mm²269 A210 A9.27 V (1.34%)680.7 V15.29 V (2.22%)1605.0 W✓ OK (≤3%)
150 mm²309 A241 A7.41 V (1.07%)682.6 V12.23 V (1.77%)1284.0 W✓ OK (≤3%)
185 mm²353 A275 A6.01 V (0.87%)684.0 V9.91 V (1.44%)1041.1 W✓ OK (≤3%)
240 mm²415 A324 A4.63 V (0.67%)685.4 V7.64 V (1.11%)802.5 W✓ OK (≤3%)
300 mm²477 A372 A3.71 V (0.54%)686.3 V6.11 V (0.89%)642.0 W✓ OK (≤3%)
400 mm²570 A445 A2.78 V (0.4%)687.2 V4.59 V (0.66%)481.5 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 100A at 300 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 100A over 300m at 690V (voltage drop: 15.89V or 2.3%).

What is the power capacity of 100A at 690V?

At unity power factor, 100A at 690V supports 119.51 kW with a standard 100A circuit breaker.