350 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 18.92V (2.74%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.72V (2.71%)
Voltage at Load671.1 VLine Loss: 11469.1 W
Max Power & Breaker418.29 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3027.05 V (438.7%)0.0 V4993.21 V (723.65%)1835050.0 WDrop High
2.5 mm²24 A18 A1816.23 V (263.22%)0.0 V2995.93 V (434.19%)1101030.0 WDrop High
4 mm²32 A25 A1135.14 V (164.51%)0.0 V1872.46 V (271.37%)688143.7 WDrop High
6 mm²41 A32 A756.76 V (109.68%)0.0 V1248.3 V (180.91%)458762.5 WDrop High
10 mm²57 A44 A454.06 V (65.81%)235.9 V748.98 V (108.55%)275257.5 WDrop High
16 mm²76 A59 A283.79 V (41.13%)406.2 V468.11 V (67.84%)172035.9 WDrop High
25 mm²101 A78 A181.62 V (26.32%)508.4 V299.59 V (43.42%)110103.0 WDrop High
35 mm²125 A97 A129.73 V (18.8%)560.3 V213.99 V (31.01%)78645.0 WDrop High
50 mm²151 A118 A90.81 V (13.16%)599.2 V149.8 V (21.71%)55051.5 WDrop High
70 mm²192 A150 A64.87 V (9.4%)625.1 V107.0 V (15.51%)39322.5 WDrop High
95 mm²232 A181 A47.8 V (6.93%)642.2 V78.84 V (11.43%)28974.5 WDrop High
120 mm²269 A210 A37.84 V (5.48%)652.2 V62.42 V (9.05%)22938.1 WDrop High
150 mm²309 A241 A30.27 V (4.39%)659.7 V49.93 V (7.24%)18350.5 WDrop High
185 mm²353 A275 A24.54 V (3.56%)665.5 V40.49 V (5.87%)14878.8 W~ ≤5%
240 mm²415 A324 A18.92 V (2.74%)671.1 V31.21 V (4.52%)11469.1 W✓ OK (≤3%)
300 mm²477 A372 A15.14 V (2.19%)674.9 V24.97 V (3.62%)9175.2 W✓ OK (≤3%)
400 mm²570 A445 A11.35 V (1.65%)678.6 V18.72 V (2.71%)6881.4 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 350A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 350A over 350m at 690V (voltage drop: 18.92V or 2.74%).

What is the power capacity of 350A at 690V?

At unity power factor, 350A at 690V supports 418.29 kW with a standard 350A circuit breaker.