32 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 16.61V (2.41%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 19.57V (2.84%)
Voltage at Load673.4 VLine Loss: 920.4 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A276.76 V (40.11%)413.2 V456.52 V (66.16%)15339.5 WDrop High
2.5 mm²24 A18 A166.06 V (24.07%)523.9 V273.91 V (39.7%)9203.7 WDrop High
4 mm²32 A25 A103.78 V (15.04%)586.2 V171.2 V (24.81%)5752.3 WDrop High
6 mm²41 A32 A69.19 V (10.03%)620.8 V114.13 V (16.54%)3834.9 WDrop High
10 mm²57 A44 A41.51 V (6.02%)648.5 V68.48 V (9.92%)2300.9 WDrop High
16 mm²76 A59 A25.95 V (3.76%)664.1 V42.8 V (6.2%)1438.1 W~ ≤5%
25 mm²101 A78 A16.61 V (2.41%)673.4 V27.39 V (3.97%)920.4 W✓ OK (≤3%)
35 mm²125 A97 A11.86 V (1.72%)678.1 V19.57 V (2.84%)657.4 W✓ OK (≤3%)
50 mm²151 A118 A8.3 V (1.2%)681.7 V13.7 V (1.98%)460.2 W✓ OK (≤3%)
70 mm²192 A150 A5.93 V (0.86%)684.1 V9.78 V (1.42%)328.7 W✓ OK (≤3%)
95 mm²232 A181 A4.37 V (0.63%)685.6 V7.21 V (1.04%)242.2 W✓ OK (≤3%)
120 mm²269 A210 A3.46 V (0.5%)686.5 V5.71 V (0.83%)191.7 W✓ OK (≤3%)
150 mm²309 A241 A2.77 V (0.4%)687.2 V4.57 V (0.66%)153.4 W✓ OK (≤3%)
185 mm²353 A275 A2.24 V (0.33%)687.8 V3.7 V (0.54%)124.4 W✓ OK (≤3%)
240 mm²415 A324 A1.73 V (0.25%)688.3 V2.85 V (0.41%)95.9 W✓ OK (≤3%)
300 mm²477 A372 A1.38 V (0.2%)688.6 V2.28 V (0.33%)76.7 W✓ OK (≤3%)
400 mm²570 A445 A1.04 V (0.15%)689.0 V1.71 V (0.25%)57.5 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 32A over 350m at 690V (voltage drop: 16.61V or 2.41%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.