50 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 50 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 18.53V (2.69%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 15.29V (2.22%)
Voltage at Load671.5 VLine Loss: 1605.0 W
Max Power & Breaker59.76 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A432.44 V (62.67%)257.6 V713.32 V (103.38%)37450.0 WDrop High
2.5 mm²24 A18 A259.46 V (37.6%)430.5 V427.99 V (62.03%)22470.0 WDrop High
4 mm²32 A25 A162.16 V (23.5%)527.8 V267.49 V (38.77%)14043.7 WDrop High
6 mm²41 A32 A108.11 V (15.67%)581.9 V178.33 V (25.84%)9362.5 WDrop High
10 mm²57 A44 A64.87 V (9.4%)625.1 V107.0 V (15.51%)5617.5 WDrop High
16 mm²76 A59 A40.54 V (5.88%)649.5 V66.87 V (9.69%)3510.9 WDrop High
25 mm²101 A78 A25.95 V (3.76%)664.1 V42.8 V (6.2%)2247.0 W~ ≤5%
35 mm²125 A97 A18.53 V (2.69%)671.5 V30.57 V (4.43%)1605.0 W✓ OK (≤3%)
50 mm²151 A118 A12.97 V (1.88%)677.0 V21.4 V (3.1%)1123.5 W✓ OK (≤3%)
70 mm²192 A150 A9.27 V (1.34%)680.7 V15.29 V (2.22%)802.5 W✓ OK (≤3%)
95 mm²232 A181 A6.83 V (0.99%)683.2 V11.26 V (1.63%)591.3 W✓ OK (≤3%)
120 mm²269 A210 A5.41 V (0.78%)684.6 V8.92 V (1.29%)468.1 W✓ OK (≤3%)
150 mm²309 A241 A4.32 V (0.63%)685.7 V7.13 V (1.03%)374.5 W✓ OK (≤3%)
185 mm²353 A275 A3.51 V (0.51%)686.5 V5.78 V (0.84%)303.6 W✓ OK (≤3%)
240 mm²415 A324 A2.7 V (0.39%)687.3 V4.46 V (0.65%)234.1 W✓ OK (≤3%)
300 mm²477 A372 A2.16 V (0.31%)687.8 V3.57 V (0.52%)187.2 W✓ OK (≤3%)
400 mm²570 A445 A1.62 V (0.24%)688.4 V2.67 V (0.39%)140.4 W✓ OK (≤3%)

FAQ — 50 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 50A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 50A over 350m at 690V (voltage drop: 18.53V or 2.69%).

What is the power capacity of 50A at 690V?

At unity power factor, 50A at 690V supports 59.76 kW with a standard 50A circuit breaker.