375 Amp Cable Size at 175 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)10× 400 mm²Drop: 0.7V (2.93%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.58V (48.26%)
Voltage at Load23.3 VLine Loss: 263.3 W
Max Power & Breaker9.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1872.5 V (7802.08%)0.0 V3088.75 V (12869.79%)702187.5 WDrop High
2.5 mm²24 A18 A1123.5 V (4681.25%)0.0 V1853.25 V (7721.87%)421312.5 WDrop High
4 mm²32 A25 A702.19 V (2925.78%)0.0 V1158.28 V (4826.17%)263320.3 WDrop High
6 mm²41 A32 A468.12 V (1950.52%)0.0 V772.19 V (3217.45%)175546.9 WDrop High
10 mm²57 A44 A280.87 V (1170.31%)0.0 V463.31 V (1930.47%)105328.1 WDrop High
16 mm²76 A59 A175.55 V (731.45%)0.0 V289.57 V (1206.54%)65830.1 WDrop High
25 mm²101 A78 A112.35 V (468.12%)0.0 V185.32 V (772.19%)42131.2 WDrop High
35 mm²125 A97 A80.25 V (334.37%)0.0 V132.38 V (551.56%)30093.7 WDrop High
50 mm²151 A118 A56.17 V (234.06%)0.0 V92.66 V (386.09%)21065.6 WDrop High
70 mm²192 A150 A40.12 V (167.19%)0.0 V66.19 V (275.78%)15046.9 WDrop High
95 mm²232 A181 A29.57 V (123.19%)0.0 V48.77 V (203.21%)11087.2 WDrop High
120 mm²269 A210 A23.41 V (97.53%)0.6 V38.61 V (160.87%)8777.3 WDrop High
150 mm²309 A241 A18.72 V (78.02%)5.3 V30.89 V (128.7%)7021.9 WDrop High
185 mm²353 A275 A15.18 V (63.26%)8.8 V25.04 V (104.35%)5693.4 WDrop High
240 mm²415 A324 A11.7 V (48.76%)12.3 V19.3 V (80.44%)4388.7 WDrop High
300 mm²477 A372 A9.36 V (39.01%)14.6 V15.44 V (64.35%)3510.9 WDrop High
400 mm²570 A445 A7.02 V (29.26%)17.0 V11.58 V (48.26%)2633.2 WDrop High

FAQ — 375 Amp Cable Size at 175 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 375A at 175 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10× 400 mm² copper cable for 375A over 175m at 24V (voltage drop: 0.7V or 2.93%).

What is the power capacity of 375A at 24V?

At unity power factor, 375A at 24V supports 9.0 kW with a standard 400A circuit breaker.