16 Amp Cable Size at 175 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.65V (2.7%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.66V (2.75%)
Voltage at Load23.4 VLine Loss: 10.4 W
Max Power & Breaker0.38 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A79.89 V (332.89%)0.0 V131.79 V (549.11%)1278.3 WDrop High
2.5 mm²24 A18 A47.94 V (199.73%)0.0 V79.07 V (329.47%)767.0 WDrop High
4 mm²32 A25 A29.96 V (124.83%)0.0 V49.42 V (205.92%)479.4 WDrop High
6 mm²41 A32 A19.97 V (83.22%)4.0 V32.95 V (137.28%)319.6 WDrop High
10 mm²57 A44 A11.98 V (49.93%)12.0 V19.77 V (82.37%)191.7 WDrop High
16 mm²76 A59 A7.49 V (31.21%)16.5 V12.35 V (51.48%)119.8 WDrop High
25 mm²101 A78 A4.79 V (19.97%)19.2 V7.91 V (32.95%)76.7 WDrop High
35 mm²125 A97 A3.42 V (14.27%)20.6 V5.65 V (23.53%)54.8 WDrop High
50 mm²151 A118 A2.4 V (9.99%)21.6 V3.95 V (16.47%)38.3 WDrop High
70 mm²192 A150 A1.71 V (7.13%)22.3 V2.82 V (11.77%)27.4 WDrop High
95 mm²232 A181 A1.26 V (5.26%)22.7 V2.08 V (8.67%)20.2 WDrop High
120 mm²269 A210 A1.0 V (4.16%)23.0 V1.65 V (6.86%)16.0 W~ ≤5%
150 mm²309 A241 A0.8 V (3.33%)23.2 V1.32 V (5.49%)12.8 W~ ≤5%
185 mm²353 A275 A0.65 V (2.7%)23.4 V1.07 V (4.45%)10.4 W✓ OK (≤3%)
240 mm²415 A324 A0.5 V (2.08%)23.5 V0.82 V (3.43%)8.0 W✓ OK (≤3%)
300 mm²477 A372 A0.4 V (1.66%)23.6 V0.66 V (2.75%)6.4 W✓ OK (≤3%)
400 mm²570 A445 A0.3 V (1.25%)23.7 V0.49 V (2.06%)4.8 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 175 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 16A at 175 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 16A over 175m at 24V (voltage drop: 0.65V or 2.7%).

What is the power capacity of 16A at 24V?

At unity power factor, 16A at 24V supports 0.38 kW with a standard 16A circuit breaker.