375 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 1.45V (0.35%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.43V (0.35%)
Voltage at Load413.6 VLine Loss: 940.4 W
Max Power & Breaker269.55 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A231.66 V (55.82%)183.3 V382.13 V (92.08%)150468.7 WDrop High
2.5 mm²24 A18 A139.0 V (33.49%)276.0 V229.28 V (55.25%)90281.2 WDrop High
4 mm²32 A25 A86.87 V (20.93%)328.1 V143.3 V (34.53%)56425.8 WDrop High
6 mm²41 A32 A57.92 V (13.96%)357.1 V95.53 V (23.02%)37617.2 WDrop High
10 mm²57 A44 A34.75 V (8.37%)380.3 V57.32 V (13.81%)22570.3 WDrop High
16 mm²76 A59 A21.72 V (5.23%)393.3 V35.83 V (8.63%)14106.4 WDrop High
25 mm²101 A78 A13.9 V (3.35%)401.1 V22.93 V (5.52%)9028.1 WDrop High
35 mm²125 A97 A9.93 V (2.39%)405.1 V16.38 V (3.95%)6448.7 WDrop High
50 mm²151 A118 A6.95 V (1.67%)408.1 V11.46 V (2.76%)4514.1 WDrop High
70 mm²192 A150 A4.96 V (1.2%)410.0 V8.19 V (1.97%)3224.3 WDrop High
95 mm²232 A181 A3.66 V (0.88%)411.3 V6.03 V (1.45%)2375.8 WDrop High
120 mm²269 A210 A2.9 V (0.7%)412.1 V4.78 V (1.15%)1880.9 WDrop High
150 mm²309 A241 A2.32 V (0.56%)412.7 V3.82 V (0.92%)1504.7 WDrop High
185 mm²353 A275 A1.88 V (0.45%)413.1 V3.1 V (0.75%)1220.0 WDrop High
240 mm²415 A324 A1.45 V (0.35%)413.6 V2.39 V (0.58%)940.4 W✓ OK (≤3%)
300 mm²477 A372 A1.16 V (0.28%)413.8 V1.91 V (0.46%)752.3 W✓ OK (≤3%)
400 mm²570 A445 A0.87 V (0.21%)414.1 V1.43 V (0.35%)564.3 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 375A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 25m at 415V (voltage drop: 1.45V or 0.35%).

What is the power capacity of 375A at 415V?

At unity power factor, 375A at 415V supports 269.55 kW with a standard 400A circuit breaker.