375 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 500 m (1640.4 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.69V (2.1%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 28.66V (6.91%)
Voltage at Load406.3 VLine Loss: 5642.6 W
Max Power & Breaker269.55 kW400A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 500m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 4633.24 V (1116.44%) | 0.0 V | 7642.67 V (1841.61%) | 3009375.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 2779.94 V (669.87%) | 0.0 V | 4585.6 V (1104.96%) | 1805625.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1737.46 V (418.67%) | 0.0 V | 2866.0 V (690.6%) | 1128515.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 1158.31 V (279.11%) | 0.0 V | 1910.67 V (460.4%) | 752343.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 694.99 V (167.47%) | 0.0 V | 1146.4 V (276.24%) | 451406.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 434.37 V (104.67%) | 0.0 V | 716.5 V (172.65%) | 282128.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 277.99 V (66.99%) | 137.0 V | 458.56 V (110.5%) | 180562.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 198.57 V (47.85%) | 216.4 V | 327.54 V (78.93%) | 128973.2 W | Drop High |
| 50 mm² | 151 A | 118 A | 139.0 V (33.49%) | 276.0 V | 229.28 V (55.25%) | 90281.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 99.28 V (23.92%) | 315.7 V | 163.77 V (39.46%) | 64486.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 73.16 V (17.63%) | 341.8 V | 120.67 V (29.08%) | 47516.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 57.92 V (13.96%) | 357.1 V | 95.53 V (23.02%) | 37617.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 46.33 V (11.16%) | 368.7 V | 76.43 V (18.42%) | 30093.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 37.57 V (9.05%) | 377.4 V | 61.97 V (14.93%) | 24400.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 28.96 V (6.98%) | 386.0 V | 47.77 V (11.51%) | 18808.6 W | Drop High |
| 300 mm² | 477 A | 372 A | 23.17 V (5.58%) | 391.8 V | 38.21 V (9.21%) | 15046.9 W | Drop High |
| 400 mm² | 570 A | 445 A | 17.37 V (4.19%) | 397.6 V | 28.66 V (6.91%) | 11285.2 W | ~ ≤5% |
FAQ — 375 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 375A at 500 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 375A over 500m at 415V (voltage drop: 8.69V or 2.1%).
What is the power capacity of 375A at 415V?
At unity power factor, 375A at 415V supports 269.55 kW with a standard 400A circuit breaker.
Related Lengths & Currents (415V)
375A · 5m (415V)375A · 10m (415V)375A · 15m (415V)375A · 20m (415V)375A · 25m (415V)375A · 30m (415V)375A · 35m (415V)375A · 40m (415V)375A · 45m (415V)375A · 50m (415V)375A · 60m (415V)375A · 70m (415V)10A · 500m (415V)16A · 500m (415V)20A · 500m (415V)25A · 500m (415V)32A · 500m (415V)40A · 500m (415V)50A · 500m (415V)63A · 500m (415V)80A · 500m (415V)100A · 500m (415V)125A · 500m (415V)160A · 500m (415V)200A · 500m (415V)