40 Amp Cable Size at 400 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.85V (1.78%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.82V (5.88%)
Voltage at Load47.1 VLine Loss: 34.2 W
Max Power & Breaker1.92 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A456.53 V (951.11%)0.0 V753.07 V (1568.89%)18261.3 WDrop High
2.5 mm²24 A18 A273.92 V (570.67%)0.0 V451.84 V (941.33%)10956.8 WDrop High
4 mm²32 A25 A171.2 V (356.67%)0.0 V282.4 V (588.33%)6848.0 WDrop High
6 mm²41 A32 A114.13 V (237.78%)0.0 V188.27 V (392.22%)4565.3 WDrop High
10 mm²57 A44 A68.48 V (142.67%)0.0 V112.96 V (235.33%)2739.2 WDrop High
16 mm²76 A59 A42.8 V (89.17%)5.2 V70.6 V (147.08%)1712.0 WDrop High
25 mm²101 A78 A27.39 V (57.07%)20.6 V45.18 V (94.13%)1095.7 WDrop High
35 mm²125 A97 A19.57 V (40.76%)28.4 V32.27 V (67.24%)782.6 WDrop High
50 mm²151 A118 A13.7 V (28.53%)34.3 V22.59 V (47.07%)547.8 WDrop High
70 mm²192 A150 A9.78 V (20.38%)38.2 V16.14 V (33.62%)391.3 WDrop High
95 mm²232 A181 A7.21 V (15.02%)40.8 V11.89 V (24.77%)288.3 WDrop High
120 mm²269 A210 A5.71 V (11.89%)42.3 V9.41 V (19.61%)228.3 WDrop High
150 mm²309 A241 A4.57 V (9.51%)43.4 V7.53 V (15.69%)182.6 WDrop High
185 mm²353 A275 A3.7 V (7.71%)44.3 V6.11 V (12.72%)148.1 WDrop High
240 mm²415 A324 A2.85 V (5.94%)45.1 V4.71 V (9.81%)114.1 WDrop High
300 mm²477 A372 A2.28 V (4.76%)45.7 V3.77 V (7.84%)91.3 W~ ≤5%
400 mm²570 A445 A1.71 V (3.57%)46.3 V2.82 V (5.88%)68.5 W~ ≤5%

FAQ — 40 Amp Cable Size at 400 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 40A at 400 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 40A over 400m at 48V (voltage drop: 0.85V or 1.78%).

What is the power capacity of 40A at 48V?

At unity power factor, 40A at 48V supports 1.92 kW with a standard 40A circuit breaker.