100 Amp Cable Size at 400 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 1.43V (2.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.06V (14.71%)
Voltage at Load46.6 VLine Loss: 142.7 W
Max Power & Breaker4.8 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1141.33 V (2377.78%)0.0 V1882.67 V (3922.22%)114133.3 WDrop High
2.5 mm²24 A18 A684.8 V (1426.67%)0.0 V1129.6 V (2353.33%)68480.0 WDrop High
4 mm²32 A25 A428.0 V (891.67%)0.0 V706.0 V (1470.83%)42800.0 WDrop High
6 mm²41 A32 A285.33 V (594.44%)0.0 V470.67 V (980.56%)28533.3 WDrop High
10 mm²57 A44 A171.2 V (356.67%)0.0 V282.4 V (588.33%)17120.0 WDrop High
16 mm²76 A59 A107.0 V (222.92%)0.0 V176.5 V (367.71%)10700.0 WDrop High
25 mm²101 A78 A68.48 V (142.67%)0.0 V112.96 V (235.33%)6848.0 WDrop High
35 mm²125 A97 A48.91 V (101.9%)0.0 V80.69 V (168.1%)4891.4 WDrop High
50 mm²151 A118 A34.24 V (71.33%)13.8 V56.48 V (117.67%)3424.0 WDrop High
70 mm²192 A150 A24.46 V (50.95%)23.5 V40.34 V (84.05%)2445.7 WDrop High
95 mm²232 A181 A18.02 V (37.54%)30.0 V29.73 V (61.93%)1802.1 WDrop High
120 mm²269 A210 A14.27 V (29.72%)33.7 V23.53 V (49.03%)1426.7 WDrop High
150 mm²309 A241 A11.41 V (23.78%)36.6 V18.83 V (39.22%)1141.3 WDrop High
185 mm²353 A275 A9.25 V (19.28%)38.7 V15.26 V (31.8%)925.4 WDrop High
240 mm²415 A324 A7.13 V (14.86%)40.9 V11.77 V (24.51%)713.3 WDrop High
300 mm²477 A372 A5.71 V (11.89%)42.3 V9.41 V (19.61%)570.7 WDrop High
400 mm²570 A445 A4.28 V (8.92%)43.7 V7.06 V (14.71%)428.0 WDrop High

FAQ — 100 Amp Cable Size at 400 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 100A at 400 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 100A over 400m at 48V (voltage drop: 1.43V or 2.97%).

What is the power capacity of 100A at 48V?

At unity power factor, 100A at 48V supports 4.8 kW with a standard 100A circuit breaker.