16 Amp Cable Size at 400 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 1.14V (2.38%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.13V (2.35%)
Voltage at Load46.9 VLine Loss: 18.3 W
Max Power & Breaker0.77 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A182.61 V (380.44%)0.0 V301.23 V (627.56%)2921.8 WDrop High
2.5 mm²24 A18 A109.57 V (228.27%)0.0 V180.74 V (376.53%)1753.1 WDrop High
4 mm²32 A25 A68.48 V (142.67%)0.0 V112.96 V (235.33%)1095.7 WDrop High
6 mm²41 A32 A45.65 V (95.11%)2.3 V75.31 V (156.89%)730.5 WDrop High
10 mm²57 A44 A27.39 V (57.07%)20.6 V45.18 V (94.13%)438.3 WDrop High
16 mm²76 A59 A17.12 V (35.67%)30.9 V28.24 V (58.83%)273.9 WDrop High
25 mm²101 A78 A10.96 V (22.83%)37.0 V18.07 V (37.65%)175.3 WDrop High
35 mm²125 A97 A7.83 V (16.3%)40.2 V12.91 V (26.9%)125.2 WDrop High
50 mm²151 A118 A5.48 V (11.41%)42.5 V9.04 V (18.83%)87.7 WDrop High
70 mm²192 A150 A3.91 V (8.15%)44.1 V6.45 V (13.45%)62.6 WDrop High
95 mm²232 A181 A2.88 V (6.01%)45.1 V4.76 V (9.91%)46.1 WDrop High
120 mm²269 A210 A2.28 V (4.76%)45.7 V3.77 V (7.84%)36.5 W~ ≤5%
150 mm²309 A241 A1.83 V (3.8%)46.2 V3.01 V (6.28%)29.2 W~ ≤5%
185 mm²353 A275 A1.48 V (3.08%)46.5 V2.44 V (5.09%)23.7 W~ ≤5%
240 mm²415 A324 A1.14 V (2.38%)46.9 V1.88 V (3.92%)18.3 W✓ OK (≤3%)
300 mm²477 A372 A0.91 V (1.9%)47.1 V1.51 V (3.14%)14.6 W✓ OK (≤3%)
400 mm²570 A445 A0.68 V (1.43%)47.3 V1.13 V (2.35%)11.0 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 400 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 16A at 400 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 16A over 400m at 48V (voltage drop: 1.14V or 2.38%).

What is the power capacity of 16A at 48V?

At unity power factor, 16A at 48V supports 0.77 kW with a standard 16A circuit breaker.