⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

400 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 0.62V (0.15%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.61V (0.15%)
Voltage at Load414.4 VLine Loss: 428.0 W
Max Power & Breaker287.52 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A98.84 V (23.82%)316.2 V163.04 V (39.29%)68480.0 WDrop High
2.5 mm²24 A18 A59.31 V (14.29%)355.7 V97.83 V (23.57%)41088.0 WDrop High
4 mm²32 A25 A37.07 V (8.93%)377.9 V61.14 V (14.73%)25680.0 WDrop High
6 mm²41 A32 A24.71 V (5.95%)390.3 V40.76 V (9.82%)17120.0 WDrop High
10 mm²57 A44 A14.83 V (3.57%)400.2 V24.46 V (5.89%)10272.0 WDrop High
16 mm²76 A59 A9.27 V (2.23%)405.7 V15.29 V (3.68%)6420.0 WDrop High
25 mm²101 A78 A5.93 V (1.43%)409.1 V9.78 V (2.36%)4108.8 WDrop High
35 mm²125 A97 A4.24 V (1.02%)410.8 V6.99 V (1.68%)2934.9 WDrop High
50 mm²151 A118 A2.97 V (0.71%)412.0 V4.89 V (1.18%)2054.4 WDrop High
70 mm²192 A150 A2.12 V (0.51%)412.9 V3.49 V (0.84%)1467.4 WDrop High
95 mm²232 A181 A1.56 V (0.38%)413.4 V2.57 V (0.62%)1081.3 WDrop High
120 mm²269 A210 A1.24 V (0.3%)413.8 V2.04 V (0.49%)856.0 WDrop High
150 mm²309 A241 A0.99 V (0.24%)414.0 V1.63 V (0.39%)684.8 WDrop High
185 mm²353 A275 A0.8 V (0.19%)414.2 V1.32 V (0.32%)555.2 WDrop High
240 mm²415 A324 A0.62 V (0.15%)414.4 V1.02 V (0.25%)428.0 W✓ OK (≤3%)
300 mm²477 A372 A0.49 V (0.12%)414.5 V0.82 V (0.2%)342.4 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.09%)414.6 V0.61 V (0.15%)256.8 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 400A at 10 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 10m at 415V (voltage drop: 0.62V or 0.15%).

What is the power capacity of 400A at 415V?

At unity power factor, 400A at 415V supports 287.52 kW with a standard 400A circuit breaker.