400 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 0.31V (0.07%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.31V (0.07%)
Voltage at Load414.7 VLine Loss: 214.0 W
Max Power & Breaker287.52 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A49.42 V (11.91%)365.6 V81.52 V (19.64%)34240.0 WDrop High
2.5 mm²24 A18 A29.65 V (7.15%)385.3 V48.91 V (11.79%)20544.0 WDrop High
4 mm²32 A25 A18.53 V (4.47%)396.5 V30.57 V (7.37%)12840.0 WDrop High
6 mm²41 A32 A12.36 V (2.98%)402.6 V20.38 V (4.91%)8560.0 WDrop High
10 mm²57 A44 A7.41 V (1.79%)407.6 V12.23 V (2.95%)5136.0 WDrop High
16 mm²76 A59 A4.63 V (1.12%)410.4 V7.64 V (1.84%)3210.0 WDrop High
25 mm²101 A78 A2.97 V (0.71%)412.0 V4.89 V (1.18%)2054.4 WDrop High
35 mm²125 A97 A2.12 V (0.51%)412.9 V3.49 V (0.84%)1467.4 WDrop High
50 mm²151 A118 A1.48 V (0.36%)413.5 V2.45 V (0.59%)1027.2 WDrop High
70 mm²192 A150 A1.06 V (0.26%)413.9 V1.75 V (0.42%)733.7 WDrop High
95 mm²232 A181 A0.78 V (0.19%)414.2 V1.29 V (0.31%)540.6 WDrop High
120 mm²269 A210 A0.62 V (0.15%)414.4 V1.02 V (0.25%)428.0 WDrop High
150 mm²309 A241 A0.49 V (0.12%)414.5 V0.82 V (0.2%)342.4 WDrop High
185 mm²353 A275 A0.4 V (0.1%)414.6 V0.66 V (0.16%)277.6 WDrop High
240 mm²415 A324 A0.31 V (0.07%)414.7 V0.51 V (0.12%)214.0 W✓ OK (≤3%)
300 mm²477 A372 A0.25 V (0.06%)414.8 V0.41 V (0.1%)171.2 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.04%)414.8 V0.31 V (0.07%)128.4 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 400A at 5 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 5m at 415V (voltage drop: 0.31V or 0.07%).

What is the power capacity of 400A at 415V?

At unity power factor, 400A at 415V supports 287.52 kW with a standard 400A circuit breaker.