400 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 2.47V (0.6%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.45V (0.59%)
Voltage at Load412.5 VLine Loss: 1712.0 W
Max Power & Breaker287.52 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A395.37 V (95.27%)19.6 V652.17 V (157.15%)273920.0 WDrop High
2.5 mm²24 A18 A237.22 V (57.16%)177.8 V391.3 V (94.29%)164352.0 WDrop High
4 mm²32 A25 A148.26 V (35.73%)266.7 V244.57 V (58.93%)102720.0 WDrop High
6 mm²41 A32 A98.84 V (23.82%)316.2 V163.04 V (39.29%)68480.0 WDrop High
10 mm²57 A44 A59.31 V (14.29%)355.7 V97.83 V (23.57%)41088.0 WDrop High
16 mm²76 A59 A37.07 V (8.93%)377.9 V61.14 V (14.73%)25680.0 WDrop High
25 mm²101 A78 A23.72 V (5.72%)391.3 V39.13 V (9.43%)16435.2 WDrop High
35 mm²125 A97 A16.94 V (4.08%)398.1 V27.95 V (6.74%)11739.4 WDrop High
50 mm²151 A118 A11.86 V (2.86%)403.1 V19.57 V (4.71%)8217.6 WDrop High
70 mm²192 A150 A8.47 V (2.04%)406.5 V13.98 V (3.37%)5869.7 WDrop High
95 mm²232 A181 A6.24 V (1.5%)408.8 V10.3 V (2.48%)4325.1 WDrop High
120 mm²269 A210 A4.94 V (1.19%)410.1 V8.15 V (1.96%)3424.0 WDrop High
150 mm²309 A241 A3.95 V (0.95%)411.0 V6.52 V (1.57%)2739.2 WDrop High
185 mm²353 A275 A3.21 V (0.77%)411.8 V5.29 V (1.27%)2221.0 WDrop High
240 mm²415 A324 A2.47 V (0.6%)412.5 V4.08 V (0.98%)1712.0 W✓ OK (≤3%)
300 mm²477 A372 A1.98 V (0.48%)413.0 V3.26 V (0.79%)1369.6 W✓ OK (≤3%)
400 mm²570 A445 A1.48 V (0.36%)413.5 V2.45 V (0.59%)1027.2 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 400A at 40 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 40m at 415V (voltage drop: 2.47V or 0.6%).

What is the power capacity of 400A at 415V?

At unity power factor, 400A at 415V supports 287.52 kW with a standard 400A circuit breaker.