400 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 1.07V (2.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.06V (2.21%)
Voltage at Load46.9 VLine Loss: 428.0 W
Max Power & Breaker19.2 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A171.2 V (356.67%)0.0 V282.4 V (588.33%)68480.0 WDrop High
2.5 mm²24 A18 A102.72 V (214.0%)0.0 V169.44 V (353.0%)41088.0 WDrop High
4 mm²32 A25 A64.2 V (133.75%)0.0 V105.9 V (220.62%)25680.0 WDrop High
6 mm²41 A32 A42.8 V (89.17%)5.2 V70.6 V (147.08%)17120.0 WDrop High
10 mm²57 A44 A25.68 V (53.5%)22.3 V42.36 V (88.25%)10272.0 WDrop High
16 mm²76 A59 A16.05 V (33.44%)31.9 V26.47 V (55.16%)6420.0 WDrop High
25 mm²101 A78 A10.27 V (21.4%)37.7 V16.94 V (35.3%)4108.8 WDrop High
35 mm²125 A97 A7.34 V (15.29%)40.7 V12.1 V (25.21%)2934.9 WDrop High
50 mm²151 A118 A5.14 V (10.7%)42.9 V8.47 V (17.65%)2054.4 WDrop High
70 mm²192 A150 A3.67 V (7.64%)44.3 V6.05 V (12.61%)1467.4 WDrop High
95 mm²232 A181 A2.7 V (5.63%)45.3 V4.46 V (9.29%)1081.3 WDrop High
120 mm²269 A210 A2.14 V (4.46%)45.9 V3.53 V (7.35%)856.0 WDrop High
150 mm²309 A241 A1.71 V (3.57%)46.3 V2.82 V (5.88%)684.8 WDrop High
185 mm²353 A275 A1.39 V (2.89%)46.6 V2.29 V (4.77%)555.2 WDrop High
240 mm²415 A324 A1.07 V (2.23%)46.9 V1.76 V (3.68%)428.0 W✓ OK (≤3%)
300 mm²477 A372 A0.86 V (1.78%)47.1 V1.41 V (2.94%)342.4 W✓ OK (≤3%)
400 mm²570 A445 A0.64 V (1.34%)47.4 V1.06 V (2.21%)256.8 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 400A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 15m at 48V (voltage drop: 1.07V or 2.23%).

What is the power capacity of 400A at 48V?

At unity power factor, 400A at 48V supports 19.2 kW with a standard 400A circuit breaker.