400 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 0.36V (0.74%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.35V (0.74%)
Voltage at Load47.6 VLine Loss: 142.7 W
Max Power & Breaker19.2 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A57.07 V (118.89%)0.0 V94.13 V (196.11%)22826.7 WDrop High
2.5 mm²24 A18 A34.24 V (71.33%)13.8 V56.48 V (117.67%)13696.0 WDrop High
4 mm²32 A25 A21.4 V (44.58%)26.6 V35.3 V (73.54%)8560.0 WDrop High
6 mm²41 A32 A14.27 V (29.72%)33.7 V23.53 V (49.03%)5706.7 WDrop High
10 mm²57 A44 A8.56 V (17.83%)39.4 V14.12 V (29.42%)3424.0 WDrop High
16 mm²76 A59 A5.35 V (11.15%)42.6 V8.82 V (18.39%)2140.0 WDrop High
25 mm²101 A78 A3.42 V (7.13%)44.6 V5.65 V (11.77%)1369.6 WDrop High
35 mm²125 A97 A2.45 V (5.1%)45.6 V4.03 V (8.4%)978.3 WDrop High
50 mm²151 A118 A1.71 V (3.57%)46.3 V2.82 V (5.88%)684.8 WDrop High
70 mm²192 A150 A1.22 V (2.55%)46.8 V2.02 V (4.2%)489.1 WDrop High
95 mm²232 A181 A0.9 V (1.88%)47.1 V1.49 V (3.1%)360.4 WDrop High
120 mm²269 A210 A0.71 V (1.49%)47.3 V1.18 V (2.45%)285.3 WDrop High
150 mm²309 A241 A0.57 V (1.19%)47.4 V0.94 V (1.96%)228.3 WDrop High
185 mm²353 A275 A0.46 V (0.96%)47.5 V0.76 V (1.59%)185.1 WDrop High
240 mm²415 A324 A0.36 V (0.74%)47.6 V0.59 V (1.23%)142.7 W✓ OK (≤3%)
300 mm²477 A372 A0.29 V (0.59%)47.7 V0.47 V (0.98%)114.1 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.45%)47.8 V0.35 V (0.74%)85.6 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 400A at 5 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 5m at 48V (voltage drop: 0.36V or 0.74%).

What is the power capacity of 400A at 48V?

At unity power factor, 400A at 48V supports 19.2 kW with a standard 400A circuit breaker.