400 Amp Cable Size at 300 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)9× 400 mm²Drop: 1.43V (2.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.18V (44.12%)
Voltage at Load46.6 VLine Loss: 570.7 W
Max Power & Breaker19.2 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3424.0 V (7133.33%)0.0 V5648.0 V (11766.67%)1369600.0 WDrop High
2.5 mm²24 A18 A2054.4 V (4280.0%)0.0 V3388.8 V (7060.0%)821760.0 WDrop High
4 mm²32 A25 A1284.0 V (2675.0%)0.0 V2118.0 V (4412.5%)513600.0 WDrop High
6 mm²41 A32 A856.0 V (1783.33%)0.0 V1412.0 V (2941.67%)342400.0 WDrop High
10 mm²57 A44 A513.6 V (1070.0%)0.0 V847.2 V (1765.0%)205440.0 WDrop High
16 mm²76 A59 A321.0 V (668.75%)0.0 V529.5 V (1103.12%)128400.0 WDrop High
25 mm²101 A78 A205.44 V (428.0%)0.0 V338.88 V (706.0%)82176.0 WDrop High
35 mm²125 A97 A146.74 V (305.71%)0.0 V242.06 V (504.29%)58697.1 WDrop High
50 mm²151 A118 A102.72 V (214.0%)0.0 V169.44 V (353.0%)41088.0 WDrop High
70 mm²192 A150 A73.37 V (152.86%)0.0 V121.03 V (252.14%)29348.6 WDrop High
95 mm²232 A181 A54.06 V (112.63%)0.0 V89.18 V (185.79%)21625.3 WDrop High
120 mm²269 A210 A42.8 V (89.17%)5.2 V70.6 V (147.08%)17120.0 WDrop High
150 mm²309 A241 A34.24 V (71.33%)13.8 V56.48 V (117.67%)13696.0 WDrop High
185 mm²353 A275 A27.76 V (57.84%)20.2 V45.79 V (95.41%)11104.9 WDrop High
240 mm²415 A324 A21.4 V (44.58%)26.6 V35.3 V (73.54%)8560.0 WDrop High
300 mm²477 A372 A17.12 V (35.67%)30.9 V28.24 V (58.83%)6848.0 WDrop High
400 mm²570 A445 A12.84 V (26.75%)35.2 V21.18 V (44.12%)5136.0 WDrop High

FAQ — 400 Amp Cable Size at 300 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 400A at 300 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 9× 400 mm² copper cable for 400A over 300m at 48V (voltage drop: 1.43V or 2.97%).

What is the power capacity of 400A at 48V?

At unity power factor, 400A at 48V supports 19.2 kW with a standard 400A circuit breaker.