425 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.31V (0.33%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.62V (0.41%)
Voltage at Load398.7 VLine Loss: 966.3 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A262.55 V (65.64%)137.4 V433.08 V (108.27%)193268.7 WDrop High
2.5 mm²24 A18 A157.53 V (39.38%)242.5 V259.85 V (64.96%)115961.2 WDrop High
4 mm²32 A25 A98.46 V (24.61%)301.5 V162.41 V (40.6%)72475.8 WDrop High
6 mm²41 A32 A65.64 V (16.41%)334.4 V108.27 V (27.07%)48317.2 WDrop High
10 mm²57 A44 A39.38 V (9.85%)360.6 V64.96 V (16.24%)28990.3 WDrop High
16 mm²76 A59 A24.61 V (6.15%)375.4 V40.6 V (10.15%)18118.9 WDrop High
25 mm²101 A78 A15.75 V (3.94%)384.2 V25.99 V (6.5%)11596.1 WDrop High
35 mm²125 A97 A11.25 V (2.81%)388.7 V18.56 V (4.64%)8282.9 WDrop High
50 mm²151 A118 A7.88 V (1.97%)392.1 V12.99 V (3.25%)5798.1 WDrop High
70 mm²192 A150 A5.63 V (1.41%)394.4 V9.28 V (2.32%)4141.5 WDrop High
95 mm²232 A181 A4.15 V (1.04%)395.9 V6.84 V (1.71%)3051.6 WDrop High
120 mm²269 A210 A3.28 V (0.82%)396.7 V5.41 V (1.35%)2415.9 WDrop High
150 mm²309 A241 A2.63 V (0.66%)397.4 V4.33 V (1.08%)1932.7 WDrop High
185 mm²353 A275 A2.13 V (0.53%)397.9 V3.51 V (0.88%)1567.0 WDrop High
240 mm²415 A324 A1.64 V (0.41%)398.4 V2.71 V (0.68%)1207.9 WDrop High
300 mm²477 A372 A1.31 V (0.33%)398.7 V2.17 V (0.54%)966.3 W✓ OK (≤3%)
400 mm²570 A445 A0.98 V (0.25%)399.0 V1.62 V (0.41%)724.8 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 425A at 25 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 25m at 400V (voltage drop: 1.31V or 0.33%).

What is the power capacity of 425A at 400V?

At unity power factor, 425A at 400V supports 294.45 kW with a standard 450A circuit breaker.