425 Amp Cable Size at 45 Meters (400V Three-Phase (IEC European Grid))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 45 m (147.6 ft).
Copper Cable (≤3% Drop)300 mm²Drop: 2.36V (0.59%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.92V (0.73%)
Voltage at Load397.6 VLine Loss: 1739.4 W
Max Power & Breaker294.45 kW450A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 45m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 472.59 V (118.15%) | 0.0 V | 779.55 V (194.89%) | 347883.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 283.55 V (70.89%) | 116.4 V | 467.73 V (116.93%) | 208730.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 177.22 V (44.31%) | 222.8 V | 292.33 V (73.08%) | 130456.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 118.15 V (29.54%) | 281.9 V | 194.89 V (48.72%) | 86970.9 W | Drop High |
| 10 mm² | 57 A | 44 A | 70.89 V (17.72%) | 329.1 V | 116.93 V (29.23%) | 52182.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 44.31 V (11.08%) | 355.7 V | 73.08 V (18.27%) | 32614.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 28.36 V (7.09%) | 371.6 V | 46.77 V (11.69%) | 20873.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 20.25 V (5.06%) | 379.7 V | 33.41 V (8.35%) | 14909.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 14.18 V (3.54%) | 385.8 V | 23.39 V (5.85%) | 10436.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 10.13 V (2.53%) | 389.9 V | 16.7 V (4.18%) | 7454.7 W | Drop High |
| 95 mm² | 232 A | 181 A | 7.46 V (1.87%) | 392.5 V | 12.31 V (3.08%) | 5492.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 5.91 V (1.48%) | 394.1 V | 9.74 V (2.44%) | 4348.5 W | Drop High |
| 150 mm² | 309 A | 241 A | 4.73 V (1.18%) | 395.3 V | 7.8 V (1.95%) | 3478.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 3.83 V (0.96%) | 396.2 V | 6.32 V (1.58%) | 2820.7 W | Drop High |
| 240 mm² | 415 A | 324 A | 2.95 V (0.74%) | 397.0 V | 4.87 V (1.22%) | 2174.3 W | Drop High |
| 300 mm² | 477 A | 372 A | 2.36 V (0.59%) | 397.6 V | 3.9 V (0.97%) | 1739.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.77 V (0.44%) | 398.2 V | 2.92 V (0.73%) | 1304.6 W | ✓ OK (≤3%) |
FAQ — 425 Amp Cable Size at 45 Meters (400V Three-Phase (IEC European Grid))
What mm² cable size is required for 425A at 45 meters (400V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 45m at 400V (voltage drop: 2.36V or 0.59%).
What is the power capacity of 425A at 400V?
At unity power factor, 425A at 400V supports 294.45 kW with a standard 450A circuit breaker.
Related Lengths & Currents (400V)
425A · 5m (400V)425A · 10m (400V)425A · 15m (400V)425A · 20m (400V)425A · 25m (400V)425A · 30m (400V)425A · 35m (400V)425A · 40m (400V)425A · 50m (400V)425A · 60m (400V)425A · 70m (400V)10A · 45m (400V)16A · 45m (400V)20A · 45m (400V)25A · 45m (400V)32A · 45m (400V)40A · 45m (400V)50A · 45m (400V)63A · 45m (400V)80A · 45m (400V)100A · 45m (400V)125A · 45m (400V)160A · 45m (400V)200A · 45m (400V)