425 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.26V (0.07%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.32V (0.08%)
Voltage at Load399.7 VLine Loss: 193.3 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A52.51 V (13.13%)347.5 V86.62 V (21.65%)38653.8 WDrop High
2.5 mm²24 A18 A31.51 V (7.88%)368.5 V51.97 V (12.99%)23192.2 WDrop High
4 mm²32 A25 A19.69 V (4.92%)380.3 V32.48 V (8.12%)14495.2 WDrop High
6 mm²41 A32 A13.13 V (3.28%)386.9 V21.65 V (5.41%)9663.4 WDrop High
10 mm²57 A44 A7.88 V (1.97%)392.1 V12.99 V (3.25%)5798.1 WDrop High
16 mm²76 A59 A4.92 V (1.23%)395.1 V8.12 V (2.03%)3623.8 WDrop High
25 mm²101 A78 A3.15 V (0.79%)396.8 V5.2 V (1.3%)2319.2 WDrop High
35 mm²125 A97 A2.25 V (0.56%)397.7 V3.71 V (0.93%)1656.6 WDrop High
50 mm²151 A118 A1.58 V (0.39%)398.4 V2.6 V (0.65%)1159.6 WDrop High
70 mm²192 A150 A1.13 V (0.28%)398.9 V1.86 V (0.46%)828.3 WDrop High
95 mm²232 A181 A0.83 V (0.21%)399.2 V1.37 V (0.34%)610.3 WDrop High
120 mm²269 A210 A0.66 V (0.16%)399.3 V1.08 V (0.27%)483.2 WDrop High
150 mm²309 A241 A0.53 V (0.13%)399.5 V0.87 V (0.22%)386.5 WDrop High
185 mm²353 A275 A0.43 V (0.11%)399.6 V0.7 V (0.18%)313.4 WDrop High
240 mm²415 A324 A0.33 V (0.08%)399.7 V0.54 V (0.14%)241.6 WDrop High
300 mm²477 A372 A0.26 V (0.07%)399.7 V0.43 V (0.11%)193.3 W✓ OK (≤3%)
400 mm²570 A445 A0.2 V (0.05%)399.8 V0.32 V (0.08%)145.0 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 425A at 5 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 5m at 400V (voltage drop: 0.26V or 0.07%).

What is the power capacity of 425A at 400V?

At unity power factor, 425A at 400V supports 294.45 kW with a standard 450A circuit breaker.